Set The Heating - IVT Greenline HT PlusC User Manual

Table of Contents

Advertisement

The heat pump is in standby mode.
The heat pump is producing hot water. You see at which temperature
the heat pump will stop and the present temperature. Note that the stop
temperature is read at the bottom of the cylinder. The hot water is a few
degrees warmer.
The heat pump and additional heat are running.
The heat pump has received signals that it should produce heating. It now
waits for the restart time to countdown to zero.
Return to the initial menu by pressing one of the buttons or turn the dial.

Set the heating

It is easy to set the heating level on the heat pump. However, before we
explain how to do this it is important to understand the relation between
the outdoor temperature, return temperature and heat curve slope. The
easiest way to explain the relation is with a heat curve.
Heat cur ve
You use the heat curve to help set the indoor temperature you would
like. The heat pump is controlled by the outdoor temperature. When the
weather becomes colder the heat pump ensures more heating is produced
automatically.
Return temperature:
The return temperature is the temperature of the water that returns to the
heat pump from the radiators. The water led out from the heat pump to the
heating system is normally 7-10ºC higher than the return temperature.
When the outdoor temperature is -10ºC and curve 4 is set, the pump
attempts to keep the return water at approximately 40ºC. If instead the
temperature is 35ºC, the fl ow water is heated until the return water is warm
enough.
Outdoor temperature:
The outdoor temperature determines how much heating the heat pump
should produce. A sensor placed outdoors sends signals to the control unit,
which then adjusts the heat pump.
Cur ve slope:
You can change the curve slope to increase or decrease the heating in the
house. The scale is between 0-10.
On delivery the heat pump curve
slope is set to position 4. This means
that the return temperature is +35ºC
when it is 0ºC outdoors.
15
Basic functions - Customer level 1
STANDBY
No rad heat required
No hotwater required
HOTWATER MODE
Heat pump only
Stop temp
53,0°
Present temp
42,0°
HEAT RAD MODE
Compr. + Add. heat
Stop temp
45,0°
Present temp
44,0°
HEAT RAD REQ
Heat pump starts
in
320 seconds
Note

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greenline ht pluse

Table of Contents