6. Maintenance and Inspection

6.1 Maintenance

To check the water supply device and the releaser often. You should avoid the condition of no water or air enter
into system, or that will influence unit's performance and reliability. You should clear the water filter regularly to
avoid unit's damage by filter's jam.
There should be dry, sanitary and ventilation around the units. To clean the side heating exchanger regularly for
keeping good heating exchanging and saving energy.
To check the operation of every process in the u nit, the operation pressure of the refrigerant system.
You should maintain or change it in time.
To check the power supply and cable connection often, there is abnormal action or bad smell about the electrical
component. If there is, please maintain or change it in time.
Please discharge all water in the water pump and water system lest freeze the water pump or water system.
You should discharge the water at the bottom of water pump if the units will stop for long time. And you
should check the units thoroughly and fill the system with water fully before power on the units again.

6.2 Trouble shooting guide

malfunction
Water in temp.
Sensor failure
Water out temp.
Sensor failure
Coil1 sensor failure(Heating mode)
Gas return sensor failure
Ambient sensor failure
Temp. is too much
different between
water-in and water-out
Anti freezing
under cooling mode
The first time freezing
protection in winter
The second time freezing
protection in winter
Coil sensor failure
(Cooling mode)
High pressure protection
Low pressure protection
Flow switch failure
Power supply connections
wrong(for 3phase unit)
3times display PP06
(Temp.
is too much different between
water-in&out)
in 30minutes
Defrosting
Communication failure
Controller
Reason
display
The sensor is open
PP 01
or short circuit
The sensor is open
PP 02
or short circuit
The sensor is open
PP 03
or short circuit
The sensor is open
PP 04
or short circuit
The sensor is open
PP 05
or short circuit
PP 06
Water volume isn't enough
PP 07
Ambient temp.too low
PP 07
Ambient temp. too low
PP 07
Ambient temp. too low
The sensor is open
PP 08
or short circuit
Refrigerant system pressure is high
EE 01
Refrigerant system pressure is low
E E02
No water/little water
EE 03
in water system.
Wrong phase or
EE 04
lack of phase power connection
Water flow volume not
enough, water pressure
EE 05
difference is too low
Defrost code
display
Wire controller and The
EE 08
PCB connection failure
3
15
resolution
Check or replace a new sensor
Check or replace a new sensor
Check or replace a new sensor
Check or replace the sensor
Check or replace the sensor
Increase water volume
Check or change the sensor
Check pressure gauge,increase the water
volume
Check pressure gauge,refeed refrigerant
Check the water flow volume,
water pump is failure or not
Check connections of power cable
Check the water flow volume,
or water system is jammed or not
Check the wire connection