Overload Current Protection Diagnosis And Solution - Century B-VMH36SD-1 Service Manual

Comfort-aire vmh 9/12/18/24 su series vmh 30/36 sd series inverter single zone ductless mini-split
Table of Contents

Advertisement

9.3.7 Overload current protection diagnosis and solution (F0)
Error Code
Malfunction conditions
Possible causes
Troubleshooting:
Check the power supply.
Is it normal?
Is there any blockage?
Check the compressor
resistance values.
Refer to [Compressor Checking].
Is it normal?
Check to make sure connections
and wiring are correct.
Check the reactor.
Is it normal?
Replace the outdoor main PCB.
Service Manual - VMH 9/12/18/24 SU & VMH30/36S D Series
F0
An abnormal current rise is detected by checking the specified
current detection circuit.
Power supply problems.
System blockage
PCB faulty
Wiring error
Compressor malfunction
34
37
Stop the unit.
Check the power supply.
Clear the blockage
Replace the compressor
Correct the connections
or replace the wires.
Replace the reactor.