Bard CMH-29 Installation Instruction

Low ambient control and compressor cutout thermostat kit for use with w18ha, w24ha, w30ha and w36ha wall-mount heat pumps

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS

Compressor Cutout Thermostat Kit
For Use with W18HA, W24HA, W30HA and W36HA
The CMH-29 is a field-installable combination of low
ambient fan cycling control and a compressor cutout
outdoor thermostat to be used with a Bard wall-
mounted heat pump.
The CMH-29 kit consists of:
8406-112 Low Ambient Fan Cycling Switch
910-2013 Relay and Compressor Cutout
Thermostat Assembly
3/8" vinyl-covered clamps
Required fasteners
7960-771 Installation Instructions
The CMH-29 kit is for use with Bard models W18HA,
W24HA, W30HA and W36HA wall-mount heat pumps.
Compressor Cutout Thermostat
Heat pump compressor operation at outdoor
temperatures below 0° is neither desirable nor
advantageous in terms of efficiency. An outdoor
thermostat can be applied to take the mechanical
heating (compressor) offline, and send the (compressor)
signal to energize electric heat in its place (to make
electric heat first stage heating). This can also be
applied to limit the quantity of available electric heat.
CMH-29
Low Ambient Control and
Wall-Mount Heat Pumps
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Example: Heat pump with 10KW second stage heat.
Once the outdoor thermostat has switched, 15KW
without compressor.
INSTALLATION
1. Disconnect all power to wall-mount unit.
2. Remove outer and inner control panel covers.
3. Remove right side condenser inlet grille.
4. Remove all three front service panels.
5. Mount 910-2013 relay assembly into unit control
panel as shown in Figure 1 on page 3. Use phillips
head screws included with kit to attach relay to
control panel.
6. Remove cover from vertical gray cable duct on
control panel to allow wire harness from installed
relay to route into it (see Figure 1).
NOTE: The unit wiring diagram (included with unit
literature assembly and also located on inner
control panel cover) can be used to wire this
kit. However, the following instructions listed
here provide the necessary connections point-
by-point.
Manual:
Supersedes: NEW
Date:
7960-771
4-14-16
Page
1 of 5

Advertisement

loading

Summary of Contents for Bard CMH-29

  • Page 1: Installation Instructions

    7960-771 Installation Instructions panel as shown in Figure 1 on page 3. Use phillips The CMH-29 kit is for use with Bard models W18HA, head screws included with kit to attach relay to W24HA, W30HA and W36HA wall-mount heat pumps.
  • Page 2 29 kit along with two (2) phillips head screws. Use 21. Apply “This unit is equipped with CMH-29 control the two screws to attach the outdoor thermostat module” label to the inside of the inner control onto the side of the control panel adjacent to the panel cover above the unit wiring diagram.
  • Page 3 FIGURE 1 Unit Control Panel Brown, Orange/Black, and Yellow/Brown wires exit control panel through bushing with blower wires Yellow/White wire from main unit wire harness, will plug into Yellow/White Wire from ODT kit Black wire to relay Brown Wire to W2 Blue Wire to B Start Relay Assembly (when part of kit)
  • Page 4: Outdoor Thermostat

    FIGURE 2 Outdoor Thermostat Mounting and Wiring OUTDOOR THERMOSTAT Manual 7960-771 Page 4 of 5...
  • Page 5 FIGURE 3 Mounting Outdoor Thermostat Bulb and/or Low Ambient Fan Cycling Switch (as applicable) ROUTE BULB FROM OUTDOOR THERMOSTAT INTO CONDENSER SECTION WITH TUBING FROM INDOOR COIL MAKE SURE COPPER IS DRESSED AWAY FROM OTHER COPPER LINES TO PREVENT RUBBING LOW AMBIENT FAN CYCLING SWITCH BULB FROM OUTDOOR...