Vingtor Stentofon SPA-V2 System Manual

Vingtor Stentofon SPA-V2 System Manual

Public address & general alarm system
Hide thumbs Also See for SPA-V2:
Table of Contents

Advertisement

ACM Integrated System
Telephone
System Manual
PUBLIC ADDRESS & GENERAL
ALARM SYSTEM
SPA-V2
TECHNICAL MANUAL
PA microphone panel
SPA-M6D
1
2
3
4
5
6
ALL
ACM Telephone System
PABX
Entertainment
Weatherproof
PA microphone & Alarm panel
Alarm panel
SPA-A6CD
ZONE 1
GENERAL
ZONE 2
GENERAL
ALARM
ABANDON
ZONE 3
ABANDON
ALARM
MANUAL
ZONE 4
MANUAL
RESET
ALARM
ZONE 5
SPARE
ZONE 6
DIM.
EMS
EMERGENCY
PA
TALK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
VOLUME
+
ALL
B
AUX
DIM
SIGN
TALK
LS zone 1
Cabins
LS zone 2
Accommodations
LS zone 3
Lifeboat area
LS zone 4
Engine
area
LS zone 5
Open deck
LS zone 6
Open deck
A100K10369 v.4.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SPA-V2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Vingtor Stentofon SPA-V2

  • Page 1 LS zone 2 Accommodations PABX LS zone 3 Lifeboat area Telephone LS zone 4 Engine area LS zone 5 Open deck Entertainment LS zone 6 Open deck System Manual PUBLIC ADDRESS & GENERAL ALARM SYSTEM SPA-V2 TECHNICAL MANUAL A100K10369 v.4.0...
  • Page 2: Table Of Contents

    2.3.3 Zones ................... 8 2.3.4 CTB Panel Input ................9 2.3.5 Panels for Alternative Priorities in SPA-V2 ........9 3 System Overview & Types .............10 System Type Name ..............10 Standard Basic PA Functions ..........11 3.2.1 PA Microphone Panel Functions ..........11 3.2.2...
  • Page 3 5.3.10 HP-30T ..................46 5.3.11 DST-100 ..................46 5.3.12 DH-30 ..................46 5.3.13 DH-50 ..................46 5.3.14 BF-560STT ................. 47 5.3.15 VES-561TF ................. 47 5.3.16 CAREEX-6T ................47 5.3.17 DSP-15EEXMNT ................ 47 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 4 Figure 43 Boards & Connectors for Alarm panel SPA-W1AR-D ................36 Figure 44 Boards & Connectors for Alarm panel SPA-W6A4 ................... 38 Figure 45 Boards & Connectors for Alarm panel SPA-W6A4-D ................39 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 5: Introduction

    Outline drawings in AutoCAD Amplifier and Entertainment manuals 1.4 Rules and Regulations The SPA-V2 Public Address and General Alarm System is designed to meet the requirements in accordance with SOLAS: - Chapter III, part B, regulation 6.4 and 6.5 - MSC.48(66) – International Life-Saving Appliance (LSA) Code - MSC/Circ.808 –...
  • Page 6: System Build-Up & Functions

    ● Alarm mute relay during PA message TEST DISCONNECTION VOLUME ● Predefined for up to 8 alarm panels (2 included & 6 optional) and SIGN TALK MENU NEXT ALARM ALARMS ALARM ServoMaster Fire alarm Talk-back alarm module ● Input for alarm start from fire exchange (with alarm generator installed) with distribution to specified zone Figure 1 Typical basic PA configuration A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 7: Optional Features

    ● External alarm warning equipment can be connected to SPA Alarm Relay Boards which have three potential free relay contacts (SPA- BASIC TERMINAL BOARD B AL-REL-V2) RELAY ALARM GEN. 900-024 BOARD Figure 4 Basic requirements, conventional vessels (DNV) A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 8: Basic Pa & Ga For Passenger Vessels

    - Alarm and microphone panels can be set to one, two or more of the six zones or all zones. - Entertainment distribution can be restricted to pre-selected zones. - Only fire crew can have zone set in default version of system. A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 9: Ctb Panel Input

    The CTB panel is optional. There is input in the system which makes the CTB panel connection to have the highest priority. When the system is used as PAGA, this input shall not be regarded as part of the system. 2.3.5 Panels for Alternative Priorities in SPA-V2 Optional 1 priority...
  • Page 10: System Overview & Types

    2x SPA-120-V2 Options required Options required Options required 1x SPA-MUL-V2 1x SPA-EE3D-V2 2x SPA-EE3-V2 2x VPA-120/VPA-240/VPA-400 1x SPA-MUL-V2 2x SPA-MUL-V2 2x SPA-EXPW 2x VPA-120/VPA-240/VPA-400 3x VPA-120/VPA-240/VPA-400 2x SPA-EXPW 3x SPA-EXPW A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 11: Standard Basic Pa Functions

    ● For muting of external alarm sound equipment when PA message is broadcasted or for muting of loudspeaker which may cause feedback to PA microphone. - Integrated relay on terminal board (X5) BASIC TERMINAL BOARD Figure 8 Alarm Mute function A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 12: Pabx Functions

    (part of SPA-xxx-V2) SINGLE 4-WIRE ENT. BOARD ● Entertainment can be turned on/off by a switch in front of rack. ENT. on/off ● Jumper for selection of emergency or normal volume override Figure 11 Entertainment, single amplifier, 4-wire override A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 13: Entertainment - 4-Wire, Multi Amplifiers

    ● Output for external alarm warning equipment through Relay Board AL-REL6-V2 with three potential free relay contacts: - General alarm, steady - General alarm, pulsing - General alarm, pulsing with mute - Manual steady - Abandon steady A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 14: External Emergency Pa Output

    3.3.9 Power Failure Control 2 ● Amplifiers operate normally from 230 VAC power supply ● Amplifiers can operate from 230 VAC emergency, supplied from an uninterruptible power supply (UPS) if 230 V mains fail. ● SPA-UPS comes with power failure outputs Figure 18 Power fail-over to 230 VAC A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 15: Rack & Equipment

    990-552 SPA-TERMINALBOARD V2 - RJ45 contacts for interface to function boards - separate volume controls for all audio inputs - zone and priority configuration jumpers A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 16: Connecting Equipment

    SIGN TALK TALK DIM. TALK TALK SPA-AC6S TALK-BACK GENERAL DIM. ABANDON TALK MANUAL RESET SPARE ALARM MICROPHONE ALARM MUTE PANELS PANEL TELEPHONE Figure 21 Basic connections to terminal board A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 17: Equipment Connectors

    > F AUDIO > F AUDIO ACTIVE > F AUDIO > -24V > +24V Figure 22 Terminal board connectors Doc no. A100K 10369 System Manual Page 17 SPA-V2 PA/GA Systems A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 18: Jumpers

    The jumpers are normally set according to project specifications at delivery, but may be changed if modifications are needed after installation. Note that some function boards have jumpers that need to be set. See the SPA-V2 Configuration & Installation manual for jumper settings. ENTERTAINMENT OUT ZONE SELECTION ALARM PRIORITY EXTERN AMPLIFIER OVERRIDE...
  • Page 19: Function Boards

    MIC. 1 VOL. MIC. 2 VOL. PRIO.2 MIC. 3 VOL. PRIO.3 PABX VOL. PRIO.4 PRIO.1 CTB/ETB VOL TALK BACK 990-552 SPA-TERMINALBOARD V3 Figure 25 Terminal board, function board connections A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 20: Spa-Chime4-V2

    Priority: abandon ship alarm: Wobbling tone, approx. 1kHz Priority: manual alarm: Continuous tone, 1 kHz ● Interconnections to main terminal board via RJ45 plugs ● Pluggable screw terminals for external connections A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 21: Spa-Ent4-V2

    >+24 V >+24 V >+24 V >+24 V >-24 V >-24 V >-24 V >-24 V >+24 V >+24 V >-24 V >-24 V Figure 29 SPA-ENT4-v2 board & connectors A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 22: Spa-Mul-V2

    EMS+ALL - EMS ONLY > SW ITCH OUT > SWITCH OUT > SWITCH OUT Doc no. A100K 10369 System Manual Page 23 Figure 31 SPA-EMS v2 board & connectors SPA-V2 PA/GA Systems A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 23: Spa-Vdr-V2

    > SWITCH OUT > SWITCH OUT X100 X100 Page 24 System Manual Doc no. A100K 10369 Page 24 System Manual Doc no. A100K 10369 SPA-V2 PA/GA Systems SPA-V2 PA/GA Systems A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 24: Vpa Amplifiers

    18 - Remote volume control 19 - Priority over entertainment input Doc no. A100K 10369 System Manual Page 25 Doc no. A100K 10369 System Manual Page 25 SPA-V2 PA/GA Systems SPA-V2 PA/GA Systems A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 25: Technical Data

    IEC 168-3 Electrical measures Safety according to CEI 65 Indicator Front VO meter, power and failure, overload lamp 19” rack mounting Mounting Table 1 Technical specifications for VPA amplifiers A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 26: Optional Function Equipment

    ● General Alarm pulsing with PA mute GA OUTPUT MUTE BY GA OUTPUT PULSING GA OUTPUT STEADY PULSING PULSING COMMON COMMON COMMON MUTE STEADY +24V X163 X162 X161 GA-ON ABANDON ON MANUAL ON X160 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 27: Spa-Rel-V2

    ● Over-load and short-circuit protected ● DNV-GL approved 4.5.8 PROMAX-240-24 Power supply 100-240VAC/24VDC 10A ● DIN Mounted additional power supply for rack equipment ● Over-load and short-circuit protected ● DNV-GL approved A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 28: Field Equipment

    Field Equipment For Mounting & Installation instructions, see SPA-V2 Configuration and Installation manual. 5.1 PA & Alarm Panels 5.1.1 SPA-M1-V2 SPA-M1 Single PA panel, all call for indoor use. ● For gooseneck mic. ETC-1-TB or handheld microphone MB-30G ● Built-in pre-amplifier with preset signal level and separate BASS &...
  • Page 29: Spa-M1-D

    < ZONE 4 < ZONE 5 < ZONE 6 < EMS > + 24VDC EMS INPUT > 0 V LOCAL MUTE Figure 36 Board & Connectors for PA panels SPA-M1-D A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 30: Spa-M6-V2

    < ZONE 6 < EMS EMS INPUT PWM INPUT SPA-M1 & SPA-M6 > + 24VDC > 0 V LOCAL MUTE Figure 37 Board & Connectors for PA panels SPA-M6-V2 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 31: Spa-M6-D

    < ZONE 4 < ZONE 5 < ZONE 6 < EMS > + 24VDC EMS INPUT > 0 V LOCAL MUTE Figure 38 Board & Connectors for PA panels SPA-M6-D A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 32: Spa-M6Boks

    START GENERAL > LAMP GENERAL > LAMP ABANDON > LAMP MANUAL EMS INPUT PWM DIMMER IN < FIRE ALL < FIRE CREW Figure 39 Board and Connectors for SPA-AC6 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 33: Spa-Ac6-D

    Wall with 4x4 mm screws Dimensions: 140W x 230H x 125D mm Cabling: Pluggable screw terminals, max 2.5 mm2 cable Cable glands: 2 x PG-16 Weight: 0.5 Kg Protection: IP66 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 34: Spa-W1-D

    Wall with 4x4 mm screws Dimensions: 140W x 230H x 125D mm Mic Connector Cabling: Pluggable screw terminals, max 2.5 mm2 cable Cable glands: 4 x PG-16 Weight: 0.5 Kg Protection: IP66 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 35: Spa-W1Ar-V2

    Wall with 4x4 mm screws Dimensions: 140W x 230H x 125D mm Cabling: Pluggable screw terminals, max 2.5 mm2 cable Cable glands: 2 x PG-16 Weight: 0.5 kg Protection: IP66 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 36: Spa-W1Ar-D

    140W x 230H x 125D mm Cabling: Pluggable screw terminals, max 2.5 mm2 cable Cable glands: 2 x PG-16 Weight: 0.7 Kg Protection: IP66 Figure 43 Boards & Connectors for Alarm panel SPA-W1AR-D A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 37: Spa-W6A4

    Wall with 4x4 mm screws Dimensions: 140W x 230H x 125D mm Cabling: Pluggable screw terminals, max 2.5 mm cable Cable glands: 2 x PG-16 Weight: 0.7 Kg Protection: IP66 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 38: Spa-W6A4-D

    Wall with 4x4 mm screws Dimensions: 140W x 230H x 125D mm Cabling: Pluggable screw terminals, max 2.5 mm cable Cable glands: 2 x PG-16 Weight: 0.7 Kg Protection: IP66 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 39: Figure 45 Boards & Connectors For Alarm Panel Spa-W6A4-D

    > 0 V < RESET < START MANUAL < START ABANDON < START GENERAL > LAMP GENERAL > LAMP ABANDON > LAMP MANUAL EMS OUT < FIRE ALL < FIRE CREW A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 40: Etc-1-Tb

    Doc no. A100K 10369 System Manual Page 43 Plug 5-pole DIN SPA-V2 PA/GA Systems Doc no. A100K 10369 System Manual Page 43 Supply 1.1 - 9V SPA-V2 PA/GA Systems Accessories Sponge windscreen A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 41: Volume Controls

    Pluggable screw terminals max 2.5 mm cable <+24 V OVER RID E Cable glands 1 x PG-29 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System < -2 4V O VER RI DE Weight Approx. 0,7 Kg System Manual <10 0 V LINE IN...
  • Page 42: Vm15-Rdf

    < -24V O VER RIDE <10 0V LINE IN <10 0V LINE IN > 10 0V LINE O UT >10 0V LINE O UT Figure 80 Drawing & wiring of volume control VM15-RD A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 43: Vm15-Rd

    < -24V O VER RIDE <10 0V LINE IN <10 0V LINE IN > 10 0V LINE O UT >10 0V LINE O UT Figure 80 Drawing & wiring of volume control VM15-RD A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 44: Spa-Boxm1

    200Ø x 247D mm Weight: 1.7 Kg Protection: IP56 5.3.3 CL-200T Loudspeaker, fl ush-mounted with steel fi re dome and backbox, 10W Technical data Mounting: Ceiling Dimensions: 199Ø x 121.5D mm Weight: 1.45 Kg Protection: IP44 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 45: Car-4T

    Horn loudspeaker 15W 100V transformer with fuse for use in deck areas, engine room, etc. Technical data Dimensions: 253W x 152H x 309D mm Weight: 1.85 Kg Protection: IP66 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 46: Jb-15T

    Weight: 3.6 Kg Protection: IP67 5.3.13 DH-50 Horn for driver DST-100, WT for use in deck areas. Technical data Dimensions: 508Ø x 505D mm Weight: 5.15 Kg Protection: IP67 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 47: Bf-560Stt

    186W x 144H x 207D mm Weight: 2.2 Kg Protection: IP-67 5.3.18 DHP/DST-40EEXENT Antistatic Horn W/ Atex App. 40W Driver Technical data Dimensions: 368W x 175H x 380D mm Weight: 4.0 Kg Protection: IP-67 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 48 220Ø x 172D mm Weight: 3,0 Kg Protection: IP-67 5.3.20 HP-20EEXIINT Loudspeaker 20W, 100V, Ex Zone 2 Technical data Dimensions: 237Ø x 286D mm Weight: 2,3 Kg Protection: IP-67 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 49 A100K10369 v4.0 SPA-V2 Public Address & General Alarm System System Manual...
  • Page 50 www.zenitel.com Zenitel Norway AS The WEEE Directive does not legislate that Zenitel, as a ‘producer’, shall collect ‘end of life’ WEEE. This ‘end of life’ WEEE should be recycled appropriately by the owner who should use proper treatment and recycling measures. It should not be disposed to landfi ll. Many electrical items that we throw away can be repaired or recycled.