Advertisement

(2) Precautions for connection
(a) Connect the FG signal line and shield of the RS-232 cable as
RS-232 cable
Connected to the screw clamp of
FG signal
the AJ65BT-R2N side connector.
Connected to the screw clamp of
the AJ65BT-R2N side connector.
Shield
(Not connected to external
device)
(b) When data communication cannot be performed normally due
(AJ65BT-R2N side)
Connector chassis
SD
RD
DSR
DTR
SG
(c) Do not connect an RS-422 device to the RS-232 interface.
follows:
Table 5.3 Precautions for connection
Connection method
to external noise, connect the wires as follows:
1) Connect the FG terminals of both stations with the shield of
the RS-232 cable.
For the external device side, refer to the handling
instructions for the external device.
2) Each signal line (except for SG) must be twisted with the
SG signal line.
3) FG of the AJ65BT-R2N is connected to the screw clamp of
the connector, acting as FG of the module.
Figure 5.2 Precautions for connection
Doing so will damage the RS-422 interface of the connected
device, resulting in communication failure.
• Do not short-circuit the FG and SG signal
lines of the RS-232 cable.
• If the FG and SG signal lines are
connected inside the external-device
side, do not connect the FG signal line on
the AJ65BT-R2N side to the external
device.
Shield
19
Remarks
(External device side)
FG
RD
SD
DTR
DSR
SG

Advertisement