HEIL FEM4X Installation Instructions Manual page 9

Fan coils
Hide thumbs Also See for FEM4X:
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Wiring Layout − Heat Pump Unit
Figure 11
(Cooling and 2−Stage Heat with
One Outdoor Thermostat)
THERMOSTAT
RED
R
GRY
G
BRN
C
WHT
W
2
VIO
E
BLU
L
O
Y
Wiring Layout − Heat Pump Unit
Figure 12
(Cooling and 2−Stage Heat with
Two Outdoor Thermostats)
THERMOSTAT
RED
R
GRY
G
BRN
C
WHT
W
2
L
E
O
Y
C
1
4
7
EMERGENCY HEAT RELAY
Wiring Layout − Heat Pump Unit
Figure 13
(Cooling and 2−Stage Heat for
Manufactured Housing)
FAN COIL
THERMOSTAT
(CONTROL)
R
G
C
W
2
E
L
O
Y
Transformer Information
Transformer is factory wired for 230V operation. For 208V
applications, disconnect the black wire from the 230V terminal
on transformer and connect it to the 208V terminal (refer to
Figure 14).
496 01 5503 00
FAN COIL
HEAT PUMP
(CONTROL)
(CONTROL)
R
R
G
C
C
W
2
E
W
2
ODTS
W
3
O
Y
FAN COIL
HEAT PUMP
(CONTROL)
(CONTROL)
R
R
G
C
C
W
2
W
2
BLU
ODTS1
W
3
VIO
E
ODTS2
O
Y
C
9
6
3
HEAT PUMP
(CONTROL)
R
R
G
C
C
W
W
2
2
W
3
E
ODTS
O
Y
Specifications are subject to change without notice.
Fan Coils: FEM4X, FEM4P, REM4X
Figure 14
Transformer Connections
SECONDARY
C. GROUND CONNECTIONS
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to establish uninterrupted or unbroken ground
could result in personal injury and/or death.
According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground
in order to minimize potential for personal injury or death
if an electrical fault should occur. The ground may consist
of electrical wire or metal conduit when installed in
accordance with existing electrical codes. If conduit
connection uses reducing washers, a separate ground
wire must be used.
NOTE: Use UL listed conduit and conduit connectors for
connecting supply wire(s) to unit to obtain proper grounding.
Grounding may also be accomplished by using grounding lugs
provided in control box.
D. MINIMUM CFM AND MOTOR SPEED SELECTION
Units with or without electric heaters require a minimum CFM.
Refer to the unit wiring label to ensure that the fan speed
selected is not lower than the minimum fan speed indicated.
FEM4X, FEM4P, and REM4X models: fan speed is
selected at the motor connector. Units with or without
electric heaters require a minimum CFM. Refer to the unit
wiring label to ensure that the fan speed selected is not lower
than the minimum fan speed indicated.
SPEED TAP SELECTION AT MOTOR CONNECTOR
Tap 1
Tap 2
Medium
Tap 3
Tap 4
Electric Heat †
Tap 5
† Electric heat airflow is same CFM as Tap 3, but with 0
sec off delay.
‡ For high static applications, see Airflow Performance
Tables for max airflow.
BROWN
RED
YELLOW
BLACK
PRIMARY
Low
90 sec off delay
90 sec off delay
High
90 sec off delay
0 sec off delay
Max ‡
0 sec off delay
9