ABB ACS550 User Manual page 151

Hide thumbs Also See for ACS550:
Table of Contents

Advertisement

ACS550 User's Manual
For other faults, or for anticipating motor overheating using a model, see
FAULT
Code Description
3501 SENSOR TYPE
Identifies the type of motor temperature sensor used, PT100 (°C), PTC (ohm) or thermistor.
See parameters 1501
0 =
NONE
1 = 1 x PT100 – Sensor configuration uses one PT 100 sensor.
• Analog output
AO
• The sensor resistance increases as the motor temperature rises, as does the voltage over the sensor.
• The temperature measurement function reads the voltage through analog input
degrees Celsius.
2 = 2 x PT100 – Sensor configuration uses two PT100 sensors.
• Operation is the same as for above 1 x PT100.
3 = 3 x PT100 – Sensor configuration uses three PT100 sensors.
• Operation is the same as for above 1 x PT100.
4 =
– Sensor configuration uses PTC.
PTC
• The analog output feeds a constant current through the sensor.
• The resistance of the sensor increases sharply as the motor
temperature rises over the PTC reference temperature (T
the voltage over the resistor. The temperature measurement function
reads the voltage through analog input
• The figure shows typical PTC sensor resistance values as a function of
the motor operating temperature.
Temperature
Normal
Excessive
5 =
(0) – Sensor configuration uses a thermistor.
THERM
• Motor thermal protection is activated through a digital input. Connect either a PTC sensor or a normally closed
thermistor relay to a digital input. The drive reads the digital input states as shown in the above table.
• When the digital input is '0' the motor is overheated.
• See the figures in the introduction to this group.
6 =
(1) – Sensor configuration uses a thermistor.
THERM
• Motor thermal protection is activated through a digital input. Connect a normally open thermistor relay to a digital
input. The drive reads the digital input states as shown in the table above.
• When the digital input is '1' the motor is overheated.
• See the figures in the introduction to this group.
3502 INPUT SELECTION
Defines the input used for the temperature sensor.
1 =
1 – PT100 and PTC.
AI
2 =
2 – PT100 and PTC.
AI
3...8 =
1...
6 – Thermistor
DI
DI
3503 ALARM LIMIT
Defines the alarm limit for motor temperature measurement.
• At motor temperatures above this limit, the drive displays an alarm (2010,
For thermistors:
0 – de-activated
1 – activated
3504 FAULT LIMIT
Defines the fault limit for motor temperature measurement.
• At motor temperatures above this limit, the drive displays a fault (9,
For thermistors:
0 – de-activated
1 – activated
FUNCTIONS.
1
and 1507
AO
CONTENT SEL
1 or
2 feeds constant current through the sensor.
AO
1 and converts it into ohms.
AI
Resistance
< 3 kohm
> 28 kohm
2
.
AO
CONTENT SEL
), as does
ref
MOTOR TEMP
MOT OVERTEMP
Group 30:
1 or
2 and converts it to
AI
AI
ohm
4000
1330
550
100
)
) and stops the drive.
Parameters
151
T

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-01Acs550-u1

Table of Contents