6.1. OPERATION

Continuous operating
Fan - thermostatic
(apart of thermostat,
mode
heating element is
Continuous operating
Fan - continous
(apart of thermostat,
mode
*At air inlet temperature 0
Room thermostat
1. Operation mode switch
2. ON/OFF switch
3. Temperature knob
4. HEAT/FAN temp. knob
The room thermostat should to be mounted at about 1.5 m above the floor in a well ventilated place. Do not mount near heat
sources, lights, windows and doors. The thermostat is equipped with a 5 meters cable 5x0,75 mm
the same type.
It is prohibited to disconnect heater direct from power supply, Unit should be disconnect by switch
be disconnected after fan stops operating (approx. 30 sec.)
| 10
www.flowair.com
SUMMER
ON
Operating as same as heating element. Cooling down time 30sec
turned off)
heating element is
turned off)
o
C
I STEP
ON
I
Δt (9kW)* = +10°C
Δt (16kW)* = +16°C
after heating element disable.
Continuous operating
II STEP
ON
II
Δt (23kW)* = +21°C
2
. If a longer cable needed use
. Power supply can
OFF
ON → OFF
All
Cooling
time 30
sec.
Cooling
time 30
sec.