Download Print this page

gefran 4t-48 Installation And Operation Manual page 4

Universal temperature indicator

Advertisement

In
t. P
(. 1 .
4
• TC/LIN input parameters
Input settings
TYPE
Type
PROBE
Probe: TC
Type of probe,
0
TC J °C
signal and scale of
1
TC J °F
main input
2
TC K °C
3
TC K °F
4
TC R °C
5
TC R °F
6
TC S °C
7
TC S °F
8
TC T °C
9
TC T °F
10
TC B °C
11
TC B °F
12
TC E °C
13
TC E °F
14
TC N °C
15
TC N °F
16
TC L °C
17
TC L °F
18
TC U °C
19
TC U °F
20
TC G °C
21
TC G °F
22
TC D °C
23
TC D °F
24
TC C °C
25
TC C °F
26
TC °C
27
TC °F
Probe: RTD
28
PT100 °C
29
PT100 °F
30 JPT100 °C
31 JPT100 °F
Probe: PTC - NTC
32
PTC °C
33
PTC °F
34
NTC °C
35
NTC °F
Probe: Voltage + Current
36
0...60mV
37
0...60mV
38 12...60mV
39 12...60mV
40
0...20mA
41
0...20mA
42
4...20mA
43
4...20mA
44
0...10V
45
0...10V
46
2...10V
47
2...10V
48
0...5V
49
0...5V
50
1...5V
51
1...5V
52 0...1V/Pot
53 0...1V/Pot
54 200mV...1V
55 200mV...1V
Probe: Custom PT100 - PTC - NTC
56
PT100
JPT
57
PTC
58
NTC
N.B.: for the version R77 are not available the probe codes 0...39, 48...51, 54...58
In case of probe non-availability, maximum and minimum limits are set to 0.
In case of custom linearization, test limits for setting LO and HI errors are given by the calibration values.
If these limits are not exceeded, they are taken into consideration as limits L_S and H_S.
Max. non-linearity error for
thermocouples (TC),
resistors (PT100) and
thermistors (PTC, NTC).
The error is calculated as
deviation from theoretical value
and is expressed as percentage of full
scale (in °C).
0
120ms
Select sampling time
1
60ms
(resolution). For linear
2
30ms
input 0...1V/POT only.
3
15ms
+4 to disable filter
(average of the last eight values sampled)
4 DIGIT
without dec. point with dec. point
0/1000
0.0/999.9
32/1832
32.0/999.9
0/1300
0.0/999.9
32/2372
32.0/999.9
0/1750
0.0/999.9
32/3182
32.0/999.9
0/1750
0.0/999.9
32/3182
32.0/999.9
-200/400
-199.9/400.0
-328/752
-199.9/752.0
44/1800
44.0/999.9
111/3272
111.0/999.9
-100/750
-100.0/750.0
-148/1382
-148.0/999.9
0/1300
0.0/999.9
32/2372
32.0/999.9
0/600
0.0/600.0
32/1112
32.0/999.9
-200/400
-199.9/400.0
-328/752
-199.9/752.0
0/2300
0.0/999.9
32/4172
32.0/999.9
0/2300
0.0/999.9
32/4172
32.0/999.9
0/2300
0.0/999.9
32/4172
32.0/999.9
Custom
Custom
Custom
Custom
-200/600
-199.9/600.0
-328/1112
-199.9/999.9
-200/600
-199.9/600.0
-328/1112
-199.9/999.9
-55/120
-55.0/120.0
-67/248
-67.0/248.0
-10/70
-10.0/70.0
14/158
14.0/158.0
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
-1999/9999
-199.9/999.9
custom linear
custom linear
custom
custom
custom
custom
custom
custom
S, R range 0...1750°C; error < 0.2% f.s. (t > 300°C) / for other range; error < 0.5% f.s.
T
error < 0.2% f.s. (t > -150°C)
B
range 44...1800°C; error < 0.5% f.s. (t > 300°C) / range 44,0...999,9; error < 1% f.s. (t > 300°C)
U
range -99,9...99,9 and -99...99°C; error < 0.5% f.s. / for other range; error < 0.2% f.s. (t > -150°C)
G
error < 0.2% f.s. (t > 300°C)
D
error < 0.2% f.s. (t > 200°C)
C
range 0...2300; error < 0.2% f.s. / for other range; error < 0.5% f.s.
NTC error < 0.5% f.s.
Tc J, K, E, N, L
error < 0.2% f.s.
PT100, JPT100 e PTC
error < 0.2% f.s.
> 14bit; 16000 divs
> 14bit; 16000 divs
> 13bit; 8000 divs
> 12bit; 4000 divs
81600G_MHW_4T48_07-2011_ENG