Download Print this page

Description Of Front Panel - gefran 4t-48 Installation And Operation Manual

Universal temperature indicator

Advertisement

"Raise" and "Lower" keys:
These keys are used for any operation that
requires a numerical parameter to be raised or
lowered. •• The speed of change is proportional
to the time the key is pressed. •• The operation
is not cyclic: once the maximum (minimum) limit
is reached, there will be no further increase
(decrease) of the value, even if the key remains
pressed.
The keys can be configured to perform
reset, hold, display of the peak value, etc. as
determined by the 't.U.' and 't.d.' parameters on
the 'In' menu.
• Power supply
!
~
23
PWR
~
24
• Thermocouples
Available thermocouples:
J, K, R, S, T, B, E, N,
L, U, G, D, C
2
- Respect polarities
- For extensions,
use compensated
cable appropriate for
1
thermocouple.
• Linear input 1V for
potentiometer
4
+
3
- 1,2V
2
R >100Ω
+
1
• Digital input
Digital input
24V, 5mA
or no-voltage contact
6
(only for R77 version)
5
Connections for keylock function through digital input (require selection +VT for the signal on contact 3)
2
3 • DESCRIPTION OF FRONT PANEL
4 • CONNECTIONS
Standard:
100 to 240Vac/dc
±10%
Optional:
11 to 27Vac/dc ±10%
50/60Hz, 3,5VA max.
• Linear input with 2-wire transmitter
-
Ri = 50Ω
+
• Linear (I) - (V)
dc current
4
linear input
20mA, Ri = 50Ω
2
1
-
+
2
3
5
+VT
19
18
7
20
17
8
21
16
9
22
15
10
23
14
11
24
13
12
• Inputs
4
+
3
+
-
2
-
+
1
4 to 20mA
dc voltage linear
-
input
2
60mV, 1V, 5V, 10V
1
+
6
OFF (open): keyboard enable
+
-
ON (closed): keyboard disable
PV display: Indication of process variable
•• Indication of 'HI' or 'Lo' out of range
•• Indication of open circuit (br) or short circuit (Er)
•• Display of configuration and calibration
messages
Label with engineering units
Function key:
Gives access to different configuration stages ••
Confirms any parameter changes
6
5
4
3
2
1
• Linear input with 3-wire transmitter
to connect for 20mA input
4
+
3
Ri = 50Ω
2
-
+
1
• Pt100 / PTC / NTC
Use wires
of adequate
3
-
thickness
(min. 1mm
)
2
PT100,
2
JPT100,
PTC, NTC
1
+
81600G_MHW_4T48_07-2011_ENG
+
S
-
T
T
2-wire PTC /
3-wire Pt100
NTC / Pt100

Advertisement

loading

This manual is also suitable for:

4t-48