1 • INSTALLATION
• Dimensions and cut-out; panel mounting
63
48
48
99
10
Panel mounting:
Fix the device with the bracket provided before making any electrical
connections.
To mount two or more devices side by side, use the cut-out dimensions
shown above.
CE MARKING: The instrument conforms to the European Directives
2004/108/CE and 2006/95/CE with reference to the generic standards:
EN 61000-6-2 (immunity in industrial environment) EN 61000-6-3 (emission
in residential environment) EN 61010-1 (safety)
MAINTENANCE: Repairs must be done out only by trained and specialized
personnel. Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol,
Trichlorethylene, etc.). Use of these solvents can reduce the mechanical
reliability of the device. Use a cloth dampened in ethyl alcohol or water to
clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes
defects caused by any use not conforming to these instructions.
81600G_MHW_4T48_07-2011_ENG
4T 48
UNIVERSAL TEMPERATURE INDICATOR
70
70
45
45
!
For correct and safe
installation, follow
the instructions and
observe the warnings
contained in this
manual.
.
INSTALLATION and
OPERATION MANUAL
SOFTWARE VERSION 3.2x
code 81600G / edition 13 - 07/2011
2 • TECHNICAL SPECIFICATIONS
Display 4 digit red LED's; digit height 10mm,
Keys 3 mechanical keys (Raise, Lower, F)
Accuracy 0.2% f.s. at 25°C ambient temperature,
Resolution
(function of settable
sample time)
Main input TC, RTD, PTC, NTC
Thermocouples J, K, R, S, T, B, E, N
Cold junction error 0,1° / °C
RTD type (scale configurable within
indicated range, with or without
decimal point)
Max. RTD line resistance
PTC type / NTC type 990Ω, 25°C / 1KΩ, 25°C
Max. non-linearity error See t.P parameter
°C / °F selection Faceplate configurable
Linear scale ranges -1999...9999
Logic input
(only R77 version)
Transmitter / Sensor Power
Supply (option)
Power supply (switching)
Fuse (inside device, not
operator serviceable)
Faceplate protection IP65
Working / Storage temperatures
Relative humidity 20 to 85%, non-condensing
use for internal use only, altitude up to 2000m
Environmental conditions of
Installation Panel mounting, extractable from front
Weight 150g
EMC conformity has been tested with the following connections
FUNCTION
TC input probe
"PT100" input probe
Power supply cable
(includes R77 version)
ts=120msec
120msec, >14bit - 16000 points
60msec, >14bit - 16000 points
(only for linear inputs)
30msec, >13bit - 8000 points
(only for linear inputs)
15msec, >12bit - 4000 points
(only for linear inputs)
60mV, 1V Ri ≥ 500KΩ; 5V, 10V Ri ≥10KΩ
20mA, Ri = 50Ω
adjustable digital filter
(IEC 584-1, CEI EN 60584-1, 60584-2)
L GOST, U, G, D, C
Custom linearization available on request
DIN 43760 (PT100), JPT100
20Ω
Configurable decimal point position,
possible 32 segment linearization
24V, 5mA (Ri = 47KΩ) isolation 1500V
or voltage-free contact
24V ±10%, 50mA
15V for transmitter, max. 50mA
1,2V for potentiometer > 100Ω
(std) 100...240Vac/dc ±10%, 50/60Hz, 5,5VA
(opt) 20...27Vac/dc ±10%, 50/60Hz, 5,5VA
100...240Vac - tipo T - 500mA - 250V
11...27Vac/dc - tipo T - 1,25A - 250V
0...50°C / -20...70°C
CABLE
LENGTH USED
0,8 mm
compensated 5 m
2
1 mm
3 m
2
1 mm
1 m
2
1

Advertisement

loading

Summary of Contents for gefran 4t-48

  • Page 1 Use a cloth dampened in ethyl alcohol or water to Weight 150g clean the external plastic case. EMC conformity has been tested with the following connections SERVICE: GEFRAN has a service department. The warranty excludes FUNCTION CABLE LENGTH USED defects caused by any use not conforming to these instructions.
  • Page 2: Description Of Front Panel

    3 • DESCRIPTION OF FRONT PANEL PV display: Indication of process variable “Raise” and “Lower” keys: •• Indication of ‘HI’ or ‘Lo’ out of range These keys are used for any operation that •• Indication of open circuit (br) or short circuit (Er) requires a numerical parameter to be raised or ••...
  • Page 3: Programming And Configuration

    Device structure: identification of boards Power board - Seal side Select transmitter voltage CPU board - Component side POWER DISPLAY Select signal at contact 3 5 • PROGRAMMING and CONFIGURATION LEVEL 1 DISPLAY Pressed for approx. 2 sec. P. U . Process variable Information display Input settings...
  • Page 4 • TC/LIN input parameters Input settings TYPE Type 4 DIGIT PROBE without dec. point with dec. point Probe: TC Type of probe, TC J °C 0/1000 0.0/999.9 t. P signal and scale of TC J °F 32/1832 32.0/999.9 main input TC K °C 0/1300 0.0/999.9...
  • Page 5 (. x . maximum • Interface for GEFRAN instrument configuration Kit for PC via the USB port (Windows environment) for GEFRAN instruments configuration: KIT PC USB / RS485 o TTL Lets you read or write all of the parameters • A single software for all models •...
  • Page 6 VAC. Resistors must be at least 2W); fit a 1N4007 diode in parallel with the coil of inductive loads that operate in DC. GEFRAN spa will not be held liable for any injury to persons and/or damage to property deriving from tampering, from any incorrect or erroneous use, or from any use not conforming to the device specifications.
  • Page 7 Gefran 4T 48 Installation Manual: Temperature Indicator Tel: +27 (0)43 743 9471 sales@industrialthermal.co.za 91 Currie Street Quigney East London 5200...

This manual is also suitable for:

4t-48