In Checking The Number Of Connected Outdoor Units And Connected Indoor Units; Outdoor/Indoor Units That Do Not Operate In A Test Operation.); After Address Setup, A Lower Number Of Connected Units Is Displayed. (There Are Outdoor/Indoor Units That Do Not Operate In A Test Operation.) - Toshiba MMY-MAP0806HT8(J)P Service Manual

Hide thumbs Also See for MMY-MAP0806HT8(J)P:
Table of Contents

Advertisement

7-5-4. In checking the number of connected outdoor units and
connected indoor units after address setup, a lower number of
connected units is displayed. (There are outdoor/indoor units
that do not operate in a test operation.)
S
a t
u t
s
The number of
connected
outdoor units is
too few.
The number of
connected indoor
units is too few.
The number of
indoor units
connected to a
group is too few in
group operation
from an indoor
remote controller.
AMP Air Conditioning
C
a
u
s
e
Miswiring of communication lines between outdoor units
or an unconnected wire ( Fig. 4). (Address setup
operation finished without recognizing a miswired
follower unit.)
Miswiring of communication lines between indoor units
or an unconnected wire ( Fig. 5). (Address setup
operation finished without recognizing a miswired indoor
unit.)
The indoor remote controller is not connected with wire.
Miswiring of the indoor remote controller
Indoor remote controller communication circuit error
If 220-240 V is incorrectly applied to the remote controller
terminal, the remote controller communication circuit
fails.
C
o
u
t n
r e
After improvement of wiring, set up the addresses again
and check the number of connected outdoor units.
After modification of wiring, set up the addresses again and
check the number of connected indoor units.
Using the main indoor remote controller connected to a group,
start a test operation, specify the unit that is not operating (the
unit not connected to the group), and then check the wiring.
Using the main indoor remote controller connected to a group,
start a test operation and then specify the unit that is not
operating (the unit not connected to the group). Remove the
quick connect terminal connected to remote controller
terminals A/B, and check the voltage. If voltage is not applied
(normally 15 to18 V), replace the PC board.