Download Print this page

Honeywell SLATE R8001S9001 Installation Instructions Manual page 11

Sub-base

Advertisement

• Enclose flame detector leadwires without armor cable in metal
cable or conduit.
• Follow directions in flame detector instructions.
Be sure loads do not exceed the terminal ratings. Refer to the
labels or terminal ratings in Table 1.
The SLATE system must be mounted in an electrical enclosure.
When mounting in an electrical enclosure, provide adequate
clearance for servicing, installation, and removal of SLATE
modules.
Maximum Wire Length
• The maximum leadwire length is 300 feet to terminal inputs
(Control, Running/Lockout Interlock)
• For remote reset leadwires, maximum length to remote
pushbutton is 1000 feet.
• For remote bus data lines, maximum cable length depends on
the number of modules connected, the noise conditions, and
the cable used. The maximum of all interconnecting wires is
4000 feet.
SLATE
Sub-Base Module
R8001S9001
11

Advertisement