Step 3: Positioning the Racks

Upon receipt of the HPC LC Series solution, the racks will need to be carefully transported
from the receiving area to the data center. Be sure to follow all unpacking, transporting, and
safety instructions included with the product. When selecting the final position of the racks,
be sure to place them in sequential order, beginning with Rack 1 on the left as viewed from
the front of the racks. The cable lengths provided are designed for that relative position. For
example, figure 1 below illustrates the proper rack positioning of a 128-node cluster solution.
The rack number is located on a label at the top rear of the cabinet.
Figure 1: Rack positioning for an HPC LC Series cluster solution
The following spatial needs should be considered when deciding where to physically place
the HPC LC Series cluster solutions:
Clearance in front of the rack unit should be a minimum of 50 inches (127 cm) to allow
for adequate airflow and serviceability.
Clearance behind the rack unit should be a minimum of 30 inches (76.2 cm) to allow for
adequate airflow and serviceability; 50 inches (127 cm) is recommended.