sensoR PURPose
2.3.3. Collector Sensor T1
Supplied with HPAK, HCOM, and HFLO systems
TYPE:
10kΩ Thermistor
USE:
REQUIRED
FUNCTIONS:
'Hot' differential operation
'Hot' energy calculation
Freeze monitoring sensor for open loop
Low temperature monitor for vacation mode
Useful collector temperature monitor
Drain back system high limit monitor
WARNINgS:
Insulate from ambient temperatures
Never install inside collector
Install on collector outlet header only
2.3.4. Low tank Sensor t2
Supplied with HPAK, HCOM, and HFLO systems
TYPE:
10kΩ Thermistor
USE:
REQUIRED
FUNCTIONS:
'Cold' differential operation
Tank high limit monitor
Low temperature monitor for vacation mode
Single Tank gas function monitor average w/T3
Relay 2 space heating setpoint
Relay 3 operation setpoint
WARNINgS:
Isolate from ambient
Ensure contact with tank wall
2.3.5. High tank Sensor t3
Supplied with HCOM systems
TYPE:
10kΩ Thermistor
USE:
OPTIONAL
FUNCTIONS:
'Cold' differential operation average with T2
Tank high limit monitor average with T2
Low temperature monitor for vacation mode
average with T2
Single Tank gas function monitor average with T2
Relay 2 space heating setpoint in place of T2
Relay 3 operation setpoint in place of T2
WARNINgS:
Isolate from ambient
Ensure contact with tank wall
To use average, use checkbox in Settings
2.3.6. t4
Supplied with HCOM systems
TYPE:
10kΩ Thermistor
USE:
OPTIONAL / REQUIRED - HCOM
FUNCTIONS:
Use for energy calculation sensor
Use for simple differential operations
HCOM - Water side HX inlet (Cold)
WARNINgS:
Isolate from ambient
Ensure contact with measuring surface or
use immersion sensor
T1
T7
RPs
T4
T
T
vfs
T6
M
2.3.7. T5
Supplied with HCOM systems
TYPE:
10kΩ Thermistor
USE:
OPTIONAL / REQUIRED - HCOM
FUNCTIONS:
Use for energy calculation / simple differential
Outdoor reset in space heating mode
WARNINgS:
Keep out of direct sunlight
2.3.8. Grundfos VFS and T6
Supplied with Pro Series and HCOM
TYPE:
Vortex Flow Sensor
USE:
OPTIONAL / REQUIRED - HCOM
INFO:
Can be moved to measure flow anywhere in the solar
system and calculate energy at that point, select sensors
for cold and hot measurement in Settings
FUNCTIONS:
Monitor flow rate for energy calculation
'Cold' energy calculation
WARNINgS:
Ensure correct VFS range is set in settings
2.3.9. Grundfos RPS and T7
Supplied with HCOM systems
TYPE:
Relative Pressure Sensor / 2 x 5VDC Analog Sensing
USE:
OPTIONAL
FUNCTIONS:
Solar system pressure monitoring
Insolation monitoring with compatible pyranometer
Electricity monitoring with compatible current transformer
T5
T3
P
T2
FIg. 2.3.3