Eeprom Abnormal - Haier 1U82SA2ERA Service Manual

Wall mounted type dc inverter free match n-series
Table of Contents

Advertisement

Check the connector connection.
Thermistor resistance check
Thermistor resistance check method:
Remove the connector of the thermistor on the PCB, and measure the resistance of thermistor using tester. The
relationship between normal temperature and resistance is shown in the value of indoor thermistor.

10.3.2 EEPROM abnormal

Indoor Display
E4: indoor EEPROM error
Indoor display
F12: Outdoor EEPROM error; Outdoor LED1 flash 1 times
Method of
The Data detected by the MCU are used to determine MCU
Malfunction
Detection
Malfunction
when the data of EEPROM is error or the EEPROM is damaged
Decision
Conditions
Supposed
Causes
Troubleshooting
* Caution Be sure to turn off power switch before connect or disconnect connector,
parts damage may be occurred.
Is it normal?
Yes
Is it normal?
Faulty EEPROM data
Faulty EEPROM
Faulty PCB
Replace the indoor or outdoor mainboard
NO
Correct the connection
NO
Replace the thermistor
Yes
Replace the indoor unit PCB
36
Seivice diagnosis