red lion CUB5 Product Manual

Miniature electronic 8-digit dual counter & rate indicator
Hide thumbs Also See for CUB5:

Advertisement

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion-controls.com
MODEL CUB5 -
MINIATURE ELECTRONIC 8-DIGIT DUAL COUNTER & RATE INDICATOR
LCD, POSITIVE REFLECTIVE OR NEGATIVE TRANSMISSIVE
!
WITH YELLOW/GREEN OR RED LED BACKLIGHTING
0.46 INCH (11.7 mm) HIGH DIGITS
!
PROGRAMMABLE DECIMAL POINT
!
DESCRIPTION
The CUB5 provides up to three functions in a single display package (rate
indicator and two counters). The display can be toggled either manually or
automatically between the rate and counter(s) display.
The CUB5 display has 0.46" (11.7 mm) high digits. The LCD display is
available in Positive Image Reflective (CUB50000), Negative Image-
Transmissive with yellow/green backlighting (CUB50010), or Negative Image-
Transmissive with red backlighting (CUB50020).
The counters may be programmed for one of eight different count modes.
The counters and rate indicator have separate scaling and decimal point
placement for read-outs in different engineering units.
Input A accepts a signal for the Count and Rate displays. Input B accepts a
signal for the Count display or direction control. In the anti-coincidence mode,
both inputs are monitored simultaneously so that no counts are lost. The final
count can be chosen as the sum or difference of the two inputs. The Rate
Indicator has programmable low (minimum) and high (maximum) update times
to provide optimal display response at any input frequency. There is a
programmable user input that can be set for one of a variety of functions.
The unit is housed in a lightweight, high-impact plastic case with a clear
viewing window. The sealed front panel meets NEMA 4X/IP65 specifications
for wash-down and/or dusty environments, when properly installed.
The CUB5 can be powered from an optional RLC Micro Line/Sensor Power
Supply (MLPS0000) attached directly to the rear of a CUB5. The MLPS0000
is powered from either a 115 or 230 VAC source.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
DIMENSIONS In inches (mm)
CAUTION: Risk of electric shock.
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
FRONT PANEL AND REMOTE RESET
!
COUNT SPEEDS UP TO 20 KHz (High Speed Input)
!
OPERATES FROM 9 to 28 VDC POWER SOURCE
!
PROGRAMMABLE PRESCALER FOR TOTALING
!
BI-DIRECTIONAL COUNTING, UP/DOWN CONTROL
!
QUADRATURE SENSING (Up to 4 Times Resolution)
!
ANTI-COINCIDENCE COUNTING (ADD/ADD & ADD/SUB)
!
SEPARATE COUNT AND RATE INPUT MODE
!
WIRE CONNECTIONS MADE VIA SCREW CLAMP TYPE
!
TERMINALS
DUAL COUNTER MODE
!
COUNT INPUT VOLTAGE UP TO +28 VDC
!
NEMA 4X/IP65 SEALED FRONT BEZEL
!
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

SPECIFICATIONS

1. DISPLAY: 8 digit LCD 0.46" (11.7 mm) high digits
Transmissive red or yellow/green backlight, or Reflective. The viewing
angle of a transmissive display is designed for viewing at eye level or above
the display. Reflective display units have a full viewing angle.
2. POWER REQUIREMENTS:
Reflective Versions: 9 to 28 VDC @ 15 mA max.
Backlight Versions: 9 to 28 VDC @ 60 mA max.
Above 24 VDC, derate operating temperature to 50°C.
Must use an RLC model MLPS or a Class 2 or SELV rated power supply.
3. MEMORY: Nonvolatile E
parameters and the count value when power is removed.
4. USER INPUT: Programmable, connect to common to activate function.
Threshold Levels: V
= 4.2 V min, V
IH
Response Time: 50 msec for Inhibit function, 100 msec for all others.
Current Sinking: Internal 40 KΩ typical. Pull-up to +5 V.
Current Sourcing: External pull-down resistor required, 2KΩ max.
5. INPUTS A and B:
Trigger Levels: V
= 4.2 V min, V
IH
Max Input Frequency: 20 KHz, 50% duty cycle.
Current Sinking: Internal 40 KΩ typical. Pulled-up to +5 V.
Current Sourcing: External pull-down resistor required, 2 KΩ max.
Filter A and B: Limits Input signal to a max. frequency of 100 Hz. Connect
to common to activate.
1
Bulletin No. CUB5-H
Drawing No. LP0268
Released 6/02
2
PROM memory retains all programming
= 0.5 V max, V
= 28 VDC.
IL
MAX
= 0.5 V max, V
= 28 VDC.
IL
MAX

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CUB5 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for red lion CUB5

  • Page 1: Specifications

    DESCRIPTION SAFETY SUMMARY The CUB5 provides up to three functions in a single display package (rate All safety related regulations, local codes and instructions that appear in the indicator and two counters). The display can be toggled either manually or manual or on equipment must be observed to ensure personal safety and to automatically between the rate and counter(s) display.
  • Page 2: Basic Operation

    If all P’s appear in the display, press the select (SEL) button and check all of the data setups. The CUB5 can be programmed to function as a single counter, dual counters, single counter with rate indication or dual counters with rate indication.
  • Page 3: Programming Menus

    Program terminal Input A serves as the add input (count increments) and Input B serves as and the Common terminal. If power is removed from the CUB5 prior to exiting the subtract input (count decrements).
  • Page 4 SCALING FOR COUNT INDICATION 10. RATE DISPLAY(rAtE dSP) The CUB5’s scale factor is factory set to 1, to provide one count on the Program the desired rate display value which corresponds to the programmed display for each pulse that is input to the unit. In many applications, there will rate input (rate INP) value.
  • Page 5: Emc Installation Guidelines

    SCALING FOR RATE INDICATION Scaling the Rate channel involves programming the CUB5 so that input pulses to the unit are scaled to the desired display units. Note: It is not necessary to increase the pulse information to obtain higher resolution.
  • Page 6: Wiring Connections

    Tip of screw should not project from hole in mounting clip. 4. Install CUB5 unit through the panel cut-out until front bezel flange contacts the panel-mounted gasket. 5. Slide the mounting clip over the rear of the unit until the mounting clip is against the back of the panel.
  • Page 7: Troubleshooting

    A dairy producer wishes to indicate the flow rate and record the total Desired Display Units x Decimal Point Position gallons of milk dispensed from its processing tank. The CUB5 is installed to SCLFAC Number of Pulses meet these requirements.
  • Page 8: Limited Warranty

    The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products...

Table of Contents