Download Print this page

Danfoss KP 15 Instructions page 3

Pressure controls

Advertisement

Manual tripping
(Electrical contacts/wiring test)
TRIP
use FINGERS
ONLY!
(Do NOT use
screwdriver)
Manual tripping
Convertible reset
KP 15, code nos.: 060-2025, 060-2028
Turn plate to desired
reset confi guration
Adjustment spindle(s) location
KP 15
A. MAN./MAN. RESET
RI5AK222 - 520H0146
LP side
Reset options
LP man.
HP-man.
KP 15, KP 17B
B. AUTO/MAN. RESET
HP side
Note:
On controls with LP and/or HP man. reset, push
corresponding LP and/or HP man. reset knob during
tripping.
LP-auto.
LP-auto.
HP-man.
HP-auto.
KP 15, KP 17W, KP 25
C. AUTO./AUTO. RESET
To resume control operation after safety cut-
out, push man. reset knob as indicated.
Note:
LP man. reset is possible only after system
pressure has risen above cut-in value.
HP man. reset is possible only after system
pressure has dropped below cut-out value.
LP-man.
HP-auto.
3

Advertisement

loading

This manual is also suitable for:

Kp 17wKp 25Kp 17b