Dry Operation; Indoor Unit Control - Fujitsu ARG60LHTA Service Instruction

Duct type inverter
Hide thumbs Also See for ARG60LHTA:
Table of Contents

Advertisement

1-3. DRY OPERATION

1-3-1 INDOOR UNIT CONTROL

The compressor rotation frequency shall change according to set temperature and room
temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the Table 3.
( Table 3 : Compressor frequency )
AO* G60LATT
( Fig.2 : Compressor Control based on Room Temperature )
When the room
temperature drops
X zone
Ts+0.5°C
J zone
Ts-1.5°C
Y zone
( Fig.3 : Indoor Fan Control )
Compressor
ON
OFF
Setting air flow
Lo
S-Lo
OFF
AMP Air Conditioning
Operating
frequency
X zone
41rps
J zone
Y zone
0rps
When the room
temperature rises
Ts+1.5°C
Ts-0.5°C
Ts : Setting temperature
10
30
60
360
120
01-03
www.ampair.co.uk | sales@ampair.co.uk
360
120
10
30
(sec)