Compressor Control - Fujitsu ARG60LHTA Service Instruction

Duct type inverter
Hide thumbs Also See for ARG60LHTA:
Table of Contents

Advertisement

1-7. COMPRESSOR CONTROL

1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in Table 7.
(Table 7 : Compressor Operation Frequency Range)
AO* G60LATT
2. OPERATION FREQUENCY CONTROL AT START UP
The compressor frequency soon after the start-up is controlled as shown in Fig. 9.
(Fig.9 : Compressor Control at Start-up)
< Normal start-up >
Immediate start-up after power-ON (cooling)
(rps)
70
54
Upper
limit
40
speed
28
Immediate start-up after power-ON (Heating Ta < 10°C)
(rps)
70
54
Upper
limit
speed
25
16
Immediate start-up after power-ON (Heating Ta > 10°C)
(rps)
70
54
Upper
limit
40
speed
28
25
16
AMP Air Conditioning
Cooling
Min
Max
15rps
78rps
90
180
Elapsed time
30
120
30
Heating
Min
Max
18rps
85rps
270
360 (sec)
300
Elapsed time
=
270
Elapsed time
www.ampair.co.uk | sales@ampair.co.uk
01-09
Dry
41rps
650 (sec)
480
560
620 650 (sec)
Ta : Outdoor temperature