Time - BEL LDX-U20 User Manual

12/24 v 20 a high performance dc-ups
Hide thumbs Also See for LDX-U20:
Table of Contents

Advertisement

LDX-U20
12 V / 24 V 20 A High Performance DC-UPS

5.2.21 TIME

Used to show and set the current RTC time. The RTC is used to time stamp the event logs.
5.2.22 PC SHUTDOWN ENABLE
Enables the PC shutdown function as explained in §3.3.
Default: Disabled
Choices: Enabled, Disabled
5.2.23 PC SHUTDOWN DELAY
Delay between start of backup and PC shutdown command sent by POWERMASTER, see §3.3 for details.
Default: 0s
Range: 0s ... 60min
Resolution: 1s
5.2.24 PC SHUTDOWN TIME
Delay between start of PC shutdown and output power OFF, see §3.3 for details.
Default: 0s
Range: 0s ... 10min
Resolution: 1s
5.2.25 PC RESTART MINIMUM OFF TIME
Minimum OFF time for PC restart, see §3.3 for details. When set to 0 the PC restart function is disabled.
Default: 0s
Range: 0s ... 60s
Resolution: 1s
5.2.26 PC OFF DETECTION CURRENT THRESHOLD
Current threshold for PC OFF detection, see §3.3 for details. When set to 0 the PC restart function is
disabled.
Default: 0A
Range: 0A ... 20A
Resolution: 0.1A
5.2.27 PC OFF DETECTION TIMER
Timer user for PC OFF detection, see §3.3 for details.
Default: 1s
Range: 1s ... 60s
Resolution: 1s
Asia-Pacific
Europe, Middle East
+86 755 298 85888
© 2017 Bel Power Solutions & Protection
North America
+353 61 225 977
+1 408 785 5200
BCG.00946_001
19

Advertisement

Table of Contents
loading

Table of Contents