LDX-U20
12 V / 24 V 20 A High Performance DC-UPS
5.2.21 TIME
Used to show and set the current RTC time. The RTC is used to time stamp the event logs.
5.2.22 PC SHUTDOWN ENABLE
Enables the PC shutdown function as explained in §3.3.
Default: Disabled
Choices: Enabled, Disabled
5.2.23 PC SHUTDOWN DELAY
Delay between start of backup and PC shutdown command sent by POWERMASTER, see §3.3 for details.
Default: 0s
Range: 0s ... 60min
Resolution: 1s
5.2.24 PC SHUTDOWN TIME
Delay between start of PC shutdown and output power OFF, see §3.3 for details.
Default: 0s
Range: 0s ... 10min
Resolution: 1s
5.2.25 PC RESTART MINIMUM OFF TIME
Minimum OFF time for PC restart, see §3.3 for details. When set to 0 the PC restart function is disabled.
Default: 0s
Range: 0s ... 60s
Resolution: 1s
5.2.26 PC OFF DETECTION CURRENT THRESHOLD
Current threshold for PC OFF detection, see §3.3 for details. When set to 0 the PC restart function is
disabled.
Default: 0A
Range: 0A ... 20A
Resolution: 0.1A
5.2.27 PC OFF DETECTION TIMER
Timer user for PC OFF detection, see §3.3 for details.
Default: 1s
Range: 1s ... 60s
Resolution: 1s