Daikin EKHBHE008BA3V3 Installation Manual page 30

Indoor unit for air to water heat pump system. for installation with restricted power supply condition 6kw
Hide thumbs Also See for EKHBHE008BA3V3:
Table of Contents

Advertisement

[C] Setup on EKRP1HB digital I/O PCB
Solar priority mode
[C-00] Solar priority mode setting: for information concerning
the EKSOLHW solar kit, refer to the installation manual of
that kit.
Alarm output logic
[C-01] Alarm output logic: defines the logic of the alarm
output on the EKRP1HB digital I/O PCB.
[C-01]=0, the alarm output will be powered when an alarm
occurs (default).
[C-01]=1, the alarm output will not be powered when an
alarm occurs. This field setting allows for distinction between
detection of an alarm and detection of a power failure to the
unit.
[C-01]
Alarm
0
Closed output
(default)
1
Open output
Bivalent operation
Applies only to installations with an auxiliary boiler (alternating
operation, parallel connected). The purpose of this function is to
determine —based on the outdoor temperature— which heating
source can/will provide the space heating, either the Daikin indoor
unit or an auxiliary boiler.
The field setting "bivalent operation" apply only the indoor unit space
heating operation and the permission signal for the auxiliary boiler.
When the "bivalent operation" function is enabled, the indoor unit will
stop automatically in space heating operation when the outdoor
temperature drops below "bivalent ON temperature" and the
permission signal for the auxiliary boiler becomes active.
When the bivalent operation function is disabled, the space heating
by indoor unit is possible at all outdoor temperatures (see operation
ranges) and permission signal for auxiliary boiler is always
disactivated.
[C-02] Bivalent operation status: defines whether bivalent
operation is enabled (1) or disabled (0).
[C-03] Bivalent ON temperature: defines the outdoor
temperature below which the permission signal for the
auxiliary boiler will be active (closed, KCR on EKRP1HB) and
space heating by indoor unit will be stopped.
[C-04] Bivalent hysteresis: defines the temperature difference
between bivalent ON temperature and bivalent OFF
temperature.
Permission signal X1–X2 (EKRP1HB)
closed
[C-04]
open
[C-03]
T
Outdoor temperature
A
CAUTION
Make sure to observe all rules mentioned in
application 5 when bivalent operation function is
enabled.
Daikin shall not be held liable for any damage
resulting from failure to observe this rule.
Installation manual
28
No power supply
No alarm
to unit
Open output
Open output
Closed output
Open output
T
A
The combination of setting [4-03]=0/2 with
bivalent operation at low outdoor temperature
can result in domestic hot water shortage.
The bivalent operation function has no impact on
the domestic water heating mode. The domestic
hot water is still and only heated by the indoor
unit.
The permission signal for the auxiliary boiler is
located on the EKRP1HB (digital I/O PCB).
When it is activated, the contact X1, X2 is closed
and open when it is disactivated. See figure for
the schematic location of this contact.
X2M
[D] Restricted power supply condition mode/Local shift value
weather dependent
[D-02] is set to 1 by default: The restricted power supply condition
mode is enabled. Do not change this value.
Local shift value weather dependent
The local shift value weather dependent field setting is only relevant
in case weather dependent set point (see field setting
dependent set point (heating operation only)" on page
selected.
[D-03] Local shift value weather dependent: determines the
shift value of the weather dependent set point around
outdoor temperature of 0°C.
T
t
[1-02]
local shift value
range
[1-03]
[1-00]
0°C
[1-01]
T
Target water temperature
t
T
Outdoor temperature
A
range
Range
local shift
Local shift value
value
[1-00], [1-01],
Applicable field setting of the weather dependent set
[1-02], [1-03]
point [1]
Outdoor temperature range
(T
[D-03]
0
1
–2°C~2°C
2
3
–4°C~4°C
4
OFF ON
SS1
X1M
YC Y1 Y2 Y3 Y4
"[1] Weather
T
A
)
Local shift value
A
2
4
2
4
EKHBH/XE008BA
Indoor unit for air to water heat pump system
4PW56301-1A
24) is