CONTENTS Getting Other Information and Publications Description of Standard Equipment ....... 18 For more information, contact these publishers: ..1 Optional CFM (QH361QH421and QH481 Only) .... 18 Important Installer Note ..........18 General Information Phase Monitor ..............18 Model Nomenclature .......... 2 Three Phase Scroll Compressor Start Up Shipping Damage ............
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard.
Series General Information MODEL NOMENCLATURE 2 – A MODEL NUMBER | FILTER OPTIONS COIL OPTIONS QH - QT Model 0Z - 0KW X - 1 Inch Fiberglass X - Standard 05 - 5KW (Standard) F - 2 Inch Fiberglass 06 - 6KW CAPACITY | 09 - 9KW P - 2 Inch Pleated...
TABLE 2 ELECTRICAL SPECIFICATIONS " " & Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes. These “Minimum Circuit Ampacity”...
TABLE 2A ELECTRICAL SPECIFICATIONS (continued from Page 3) " " & Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. Based on 75° C copper wire. All wiring must conform to the National Electrical Code and all local codes. These “Minimum Circuit Ampacity”...
FIGURE 2 SHIPPING DAMAGE AIR SEAL UNDER QT UNIT Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
HANDLING UNIT AFTER REMOVAL The wheels of the unit must be locked. If the wheels were allowed to roll, the unit could roll off the cart. FROM SKID The unit should always be carted from the left side. This is the side where the compressor is located. See WARNING Figure 4.
For hot water coil option a QPBHWxx-F for free blow DUCT WORK or QPBHWxx-D for ducted airflow is used Any heat pump is more critical of proper operating When used with a ducted supply, a QCX Cabinet charge and an adequate duct system than a straight air Extension can be used to conceal the duct work above conditioning unit.
CONDENSATE DRAIN FRESH AIR INTAKE There are two drain connections on the unit. The side This unit is equipped with a fresh air damper assembly. drain is located on the bottom right side of the unit. The damper blade is locked in the closed position when The rear drain is an optional drain, and is located on the the unit is shipped from the Factory.
SERVICE LIGHT FIGURE 11 REAR DRAIN (TOP VIEW) The unit is equipped with a service light which signals DRAIN LINE the user that service is required. The light is located in the upper control panel and is visible only when the hinged service/filter access door is open.
INSTALLATION INSTRUCTIONS alignment to the mounting brackets. This unit MOUNTING THE UNIT must be level from side to side. If adjustments When installing a QT unit near an interior wall on the are necessary, shim up under the rollers with left side, a minimum of 8 inches is required;...
CONTROL BLOCK The subbase of the thermostat is factory wired to the front panel of the unit. Compatible for use with Bard INDOOR BLOWER CS2000 Controller and Energy Recovery Ventilator. The Climate Control Option D is an electronic, DEHUMIDIFICATION programmable thermostat.
TABLE 4 WALL THERMOSTATS AND SUBBASE COMBINATIONS c i t t i s FIGURE 15 THERMOSTAT PLUG TERMINALS BLOWER MOTOR P2 AND P4 LOW VOLTAGE PLUG (VIEWED FROM PIN END) (VIEWED FROM PIN END) MIS-1285 Manual 2100-379 Page...
START UP DESCRIPTION OF STANDARD IMPORTANT INSTALLER NOTE EQUIPMENT For improved start-up performance, wash the indoor coil with a dishwasher detergent. Solid State Electronic Heat Pump Control Provides efficient 30 minute defrost cycle. A thermistor sensor and speed up terminal for service along with a 10 PHASE MONITOR minute defrost override are standard on the electronic heat pump control.
f. If unit is attached to duct work, remove upper All three phase scroll compressors used in the QT cabinet extension by removing the top center series are wired identically internally. As a result, once screw only from the cabinet side panel. the correct phasing is determined for a specific system or installation, connecting properly phased power leads g.
VENT OPTIONS 2. The power connectors for the CRV (located on the right side of the unit) must be disconnected. BAROMETRIC FRESH AIR DAMPER (Standard) Squeeze the tabs on the sides of the connector and pull straight out. Unplug both of the Before starting, make sure the power has been turned connectors.
SEQUENCE OF OPERATION OPTIONAL CLIMATE CONTROLS SEQUENCE OF OPERATION Cooling – Circuit R-Y makes the thermostat pull in the compressor contactor starting the compressor and The Climate Control Option A is an electronic, non- outdoor motor. The G (indoor motor) circuit is programmable manual or auto changeover thermostat.
FIGURE 21 HEAT PUMP CONTROL BOARD MIS-973 DEFROST CYCLE If some abnormal or temporary condition such as a high wind causes the heat pump to have a prolonged defrost The defrost cycle is controlled by temperature and time cycle, the heat pump control will restore the system to on the solid state heat pump control.
SOLID STATE HEAT PUMP CONTROL CHECKING TEMPERATURE SENSOR TROUBLESHOOTING PROCEDURE 1. Disconnect temperature sensor from board and from outdoor coil. 1. Turn on AC power supply to indoor and outdoor units. 2. Use an ohmmeter and measure the resistance of the sensor.
FAN BLADE SETTING DIMENSIONS REFRIGERANT CHARGE Any service work requiring removal or adjustment in The correct system R-22 charge is shown on the unit the fan and/or motor area will require that the rating plate. Optimum unit performance will occur with dimensions in Table 7 be checked and blade adjusted in a refrigerant charge resulting in a suction line or out of the motor shaft accordingly.
TABLE 10 COOLING PRESSURE (All Temperatures in Degrees F) " Low side pressure ± 2 psig High side pressure ± 5 psig Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instructions.