Check After Address Setup When Central Control System Is Connected - Toshiba MMY-MAP0804FT8(ZG)-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804FT8(ZG)-E:
Table of Contents

Advertisement

7-4-4. Check after Address Setup when Central Control System Is Connected

When the central control system is connected, check that the following setup has finished after address setup.
Central remote
controller
U1
U2
U3
U4
Line address = 2
Other refrigerant line
U3
U1
U2
(5)
Relay
(1) Is the relay connector of the header unit connected after address setup?
connector
(2) Is the relay connector of the follower unit removed?
Terminal
(3) Is the end resistance (SW30-bit 2) of the header unit with the smallest line address number
resistance
in the central control turned on? (Setup is unnecessary for follower units.)
(4) Is the terminal resistance (SW30-bit 2) of the header units, except for the line with the
smallest central control line address, turned off? (Setup is unnecessary for follower units.)
Line address (5) Are addresses in the line address (SW13, SW14) not duplicated in each refrigerant line?
NOTE
The figure above does not show all the electric wires.
For details, refer to the installation manuals for the outdoor unit, indoor unit, remote controller, or optional
devices.
AMP Air Conditioning
(4)
(1)
Header unit (A)
Header unit (A)
U4
Outdoor unit
U5
U6
Indoor unit
Main check items
(5)
(3)
Line address = 1
Follower unit (B)
U3
U4
U1
U2
U5
U6
U1
U2
U1
U2
U1
U2
U1
A B
A B
Remote
Remote
controller
controller
– 140 –
www.ampair.co.uk | sales@ampair.co.uk
(2)
To other refrigerant line
Follower unit (C)
U3
U4
U3
U4
U5
U6
U1
U2
U5
U2
U1
U2
A B
A B
Remote
controller
Check