Range RANGE MODEL CODE SCF-20N 20050326 SCF-20N (pack of 2) 20050328 SCF-20N (pack of 7) 20050329 Contents CONTENTS System layout ........3 Identification .
System layout SYSTEM LAYOUT 1120 1086 (*) Alternative Collector collector return outlet (**) Alternative collector outlet Collector probe socket The outlet and the return must be connected to opposite sides. Glass 3,2 mm. Direction of flow of heat transfer liquid Collector return (**)
Technical specifications TECHNICAL SPECIFICATIONS DESCRIPTION Total area 2,02 Exposed area 1,81 Effective absorption area 1,77 Connections (copper pipe) 4 x Ø 22 Empty weight Liquid content Recommended flow rate for each line per m of collector l/(h x m Minimum flow rate for each line per m of collector l/(h x m Maximum flow rate for each line per m...
Connections CONNECTIONS ring nut olive olive straight union ring nut plugs sensor pocket toward the heat transfer circuit straight union ring nut ring nut olive pipe olive installation pipe ring nut installation straight union ring nut from the heat transfer circuit olive ring nut olive...
Unpacking the product UNPACKING THE PRODUCT The solar collectors are packed in various ways depending on the number of units supplied: A Packages of 1 or 2 collectors B Packages of 7 collectors Pallet contents: - collector - document envelopes containing instruction manuals, test certificate and bar code label.
Installation INSTALLATION GENERAL INSTRUCTIONS the system sustains the greatest thermal load in the winter (as in systems that combine domestic hot water production Assembly with central heating), install the collectors facing south (or The system must be installed by specialist personnel. Use south-east or south-west) at an angle greater than 35°.
Filling the circuit FILLING THE CIRCUIT Perform the following steps before starting up the system. 1 - FLUSHING AND SEAL TESTING THE SYSTEM If copper piping has been used and joints have been hot brazed, flush out the system to remove any brazing resi- dues.
Pressure at boiler up to 15 m 3 bar 15 - 20 m 3,5 bar 20 - 25 m 4 bar 25 - 30 m 4,5 bar General rule: p [bar] = 1.5 + H [m] / 10 Checks CHECKS On completion of the installation, perform the checks listed in the table below.