9 TROUBLESHOOTING
Error
Error
code
detection
Sufficient data to execute the specified operation was not
19
Slave node
provided.
20
Slave node The specified attribute is not supported.
21
Slave node The service provided excessive data.
22
Slave node The specified object does not exist in a slave node.
50
QJ71DN91 The response data format is invalid.
55
QJ71DN91 The specified slave node number is other than 0 to 63.
57
QJ71DN91 The sequence of the division reception is invalid.
257
QJ71DN91 The data length set in the buffer memory is 241 or more.
An invalid value was set as a command number in the message
258
QJ71DN91
communication command area of the buffer memory.
300
QJ71DN91 The local node is offline.
301
QJ71DN91 An error occurred during data queuing.
302
QJ71DN91 A timeout occurred while waiting for a response.
303
QJ71DN91 An invalid response was obtained.
304
QJ71DN91 A node number being used for a reserved node was specified.
305
QJ71DN91 A message was sent to the local node.
317
Slave node The response data length is too long.
9 - 10
Description
Corrective action
• Check that the specified MAC ID, class ID, instance ID and
attribute ID are correct.
• In case of attribute write, verify that the specified data is
sufficient and the data length is correct.
• Referring to the slave node manual, check the condition under
which the slave node notifies this error, and take an appropriate
action.
• Check that the specified MAC ID, class ID, instance ID and
attribute ID are correct.
• Referring to the slave node manual, check the condition under
which the slave node notifies this error, and take an appropriate
action.
• Set the data to be returned by the slave node to 240 bytes or
less.
• Check that the specified MAC ID, class ID, instance ID and
attribute ID are correct.
• Referring to the slave node manual, check the condition under
which the slave node notifies this error, and take an appropriate
action.
• Check the entire network and slave node statuses such as
whether or not a terminal resistor is disconnected.
• Specify a slave node number between 0 and 63.
• Check the entire network and slave node statuses such as
whether or not a terminal resistor is disconnected.
• Set the data length to 240 bytes or less.
• Set a command number to either
0001
, 0101
, 0102
, 0201
or FE∗∗
H
H
H
H
• Turn ON Y11 to set the local node online.
• Execute a hardware test to verify whether or not hardware is
normal.
• Check the entire network and slave node statuses such as
whether or not a terminal resistor is disconnected.
• Check the entire network and slave node statuses such as
whether or not a terminal resistor is disconnected.
• Set a node number that is not being used for a reserved node.
• Specify a node other than the local node to send messages.
• Verify that the transmission message can be responded by a
slave node.