ABB REQ650 Product Manual page 77

Breaker protection req650 ansi
Hide thumbs Also See for REQ650:
Table of Contents

Advertisement

ABB
Breaker protection REQ650 ANSI
Product version: 1.1
Table 59. Disturbance recorder DRPRDRE
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and
maximum number of channels, typical value)
Table 60. Station battery supervision SPVNZBAT
Function
Lower limit for the battery
terminal voltage
Reset ratio, lower limit
Upper limit for the battery
terminal voltage
Reset ratio, upper limit
Timers
Table 61. Insulation gas monitoring function SSIMG (63)
Function
Pressure alarm
Pressure lockout
Temperature alarm
Temperature lockout
Timers
Range or value
(60-140) % of Vbat
<105 %
(60-140) % of Vbat
>95 %
(0.000-60.000) s
Range or value
0.00-25.00
0.00-25.00
-40.00-200.00
-40.00-200.00
(0.000-60.000) s
1MRK 505 269-BUS -
Issued: April 2011
Value
40
96
340 seconds (100 recordings) at
50 Hz
280 seconds (80 recordings) at 60
Hz
Accuracy
± 1.0% of set battery voltage
-
± 1.0% of set battery voltage
-
± 0.5% ± 110 ms
Accuracy
-
-
-
-
± 0.5% ± 110 ms
77