Advertisement

12.1.3 Cooling Operation

12.1.3.1

Thermostat control

Compressor is OFF when Water Outlet Temperature – Internal Water Setting Temperature > -1.5°C for
continuously 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature – Water Inlet Temperature
(temperature at thermostat OFF is triggered) >3°C.
12.1.3.2
Cool Mode Operation
1
3 ways valve control:
3 ways valve switch and fix to cooling side.
o
2
Heat pump operates follow normal cooling operation.
3
Room heater DOES NOT operate during cool mode.
4
2 ways valve control:
2 ways valve is closed.
o
12.1.4 Target Water Temperature Setting
12.1.4.1
Target Water Temperature Control of Standard System (Optional PCB not
connected)
There are 2 types of temperature control selection which are Compensation and Direct.
Temperature control type selection by installer:
1) Compensation : Wlo, WHi, ODLo, ODHi can be set at installer menu.
2) Direct
Remote control setting by user:
1) Compensation : Shift value ±5°C from the compensation curve
2) Direct
*This setting at is only able to set when the room sensor select as Water Temperature.
*Instead of water temperature, user will set target room temperature when room sensor select as Room Thermistor
or Internal Room Thermostat.
Target water temperature is calculated as below condition.
Target water temperature = A (Base temperature) + B (shift temperature)
-
A (Base Temperature)
B (shift temperature) value is depend on the room sensor selection at remote controller as below table:
-
B (Shift Temp.)
Water temperature
External Room Thermostat
Internal Room Thermostat
&
Room Thermistor
: Direct Water Temperature Set
: Direct water temperature set change
Value from the curve + User shift value set
B shift value is depend on the room sensor selection at remocon as table below
B = 0
B = 0
Cool Mode:
B = 0 ; when Zone OFF or Zone Room Thermo OFF
B = 1 * (room set temp. (R/C) – actual room temp.)
Max/Min Regulation of B: (Max: 5°C ; Min: -5°C)
Heat Mode:
B = 0 ; when Zone OFF or Zone Room Thermo OFF
B = follow Heating PI control contents
Compensation
Sensor Selection
98
Direct
Direct value from user setting