Panasonic WH-SDC09H3E8 Service Manual page 171

Aquarea high performance series air to water heat pump
Hide thumbs Also See for WH-SDC09H3E8:
Table of Contents

Advertisement

16.5.11 Abnormal Zone 1 Sensor (H43)
1
Faulty connector connection.
2
Faulty buffer tank sensor.
3
Faulty indoor sub PCB.
Abnormality Judgment:
Continue for 5 seconds.
Troubleshooting:
Abnormal zone 1 sensor
Check the turn off power check connector connection
Normal?
Check plug out connector from zone 1 connector sub PCB in
the PCB measure resistance of zone 1 sensor characteristic
match?
Defective PCB
Replace PCB
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Caution
YES
YES
171
NO
Poor contact
Correct connection
NO
Defective zone sensor
Defective zone sensor
Replace sensor