DATA
5
5-1. REFILLING REFRIGERANT CHARGE (R410A: oz, kg)
Service Ref.
100 ft
110 ft
30 m
33 m
194 oz
200 oz
PUZ-HA30NHA5
PUZ-HA36NHA5
5.5 kg
5.7 kg
5-2. COMPRESSOR TECHNICAL DATA
Service Ref.
Compressor model
U-V
Winding Resistance
U-W
( " )
W-V
5-3. NOISE CRITERION CURVES
PUZ-HA30NHA5
PUZ-HA36NHA5
90
80
70
60
50
40
30
20
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
10
63
125
250
BAND CENTER FREQUENCIES, Hz
OCH607
120 ft
130 ft
140 ft
37 m
40 m
43 m
206 oz
212 oz
218 oz
5.9 kg
6.0 kg
6.2 kg
Additional charge is required for pipes longer than 100 ft .
(at 68°F [20°C])
PUZ-HA30NHA5
PUZ-HA36NHA5
ANB33FJEMT
0.188
0.188
0.188
SPL(dB)
MODE
LINE
COOLING
52
HEATING
53
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
500
1000
2000
4000
8000
Piping Length ( one way )
150 ft
160 ft
165 ft
180 ft
46 m
49 m
50 m
55 m
224 oz
230 oz
237 oz
242 oz
6.4 kg
6.6 kg
6.7 kg
6.9 kg
MICROPHONE
3.3 ft
5 ft
8
200 ft
210 ft
230 ft
245 ft
61 m
64 m
70 m
75 m
254 oz
260 oz
272 oz
280 oz
7.2 kg
7.4 kg
7.7 kg
7.9 kg
UNIT
GROUND
Factory
Charged
195 oz
5.5 kg