(5) Operation data during emergency operation
During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation
are set to the following values:
Operation data
Intake temperature (TH1)
Indoor liquid temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Outdoor liquid temperature (TH3)
Outdoor 2-phase pipe temperature (TH6)
Outdoor ambient temperature (TH7)
Temperature difference code
(intake temperature−set temperature) (Tj)
Discharge superheat (SHd)
Sub-cool (SC)
*1: If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data.
If the unit enters emergency operation because TH values have become mismatched, setting the thermistors
to open/short corrects the settings.
*2: If one thermistor is set to open/short, the values for each will be different.
[Example] When pipe temperature thermistor (TH3) has an open or short circuit.
Thermistor
TH3
TH6
TH4
TH5
TH2
Discharge superheat (SHd)
Cooling = TH4−TH6 = Tc−Ta
Heating = TH4− TH5 = Td−(122°F [50:])
Degree of subcooling (SC)
Cooling = TH6−TH3 = Ta−(113°F[45:])
Heating = TH5−TH2 = 122°F−113°F = 9°F
OCH607
COOL
81°F [27:]
41°F [5:]
41°F [5:]
77°F [25:]
113°F [45:]
122°F [50:]
95°F [35:]
54°F [30:]
9°F [5:]
COOL
113°F [45:]
Ta
Regard normal figure as effective data.
Tc
Regard normal figure as effective data.
41°F [5:]
41°F [5:]
[50:−45: = 5:]
Operation mode
HEAT
69°F [20.5:]
113°F [45:]
122°F [50:]
72°F [22:]
41°F [5:]
41°F [5:]
45°F [7:]
5
5
54°F [30:]
9°F [5:]
HEAT
41°F [5:]
Tb
Td
122°F [50:]
122°F [50:]
54
Remarks
(*1)
(*1)
(*1)
(*1)
(*2)