CommScope Quareo 4000 Installation Instructions Manual
CommScope Quareo 4000 Installation Instructions Manual

CommScope Quareo 4000 Installation Instructions Manual

Network chassis

Advertisement

Quick Links

ADCP-92-309
Issue 4, July 2016
Content
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2
UNPACKING AND INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3
CHASSIS INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.1
3.2
3.3
3.4
3.5
3.6
4
TECHNICAL ASSISTANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
300001739168 Rev B
www.commscope.com
Quareo 4000 Network Chassis
Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Quareo Cross-Connect Solution Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Grounding Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Power Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.4.1
AUX Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4.2
Interface Connection Ethernet Port (RJ45 Connector) PoE Switch . . . . . . . . . . . . . . . . . . . . . . . . . 9
Blade Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.6.1
LC or MPO Trunk Cable Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.6.2
LC Array Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.6.3
LC Trunk Cable Installation LC to LC Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.6.4
MPO Trunk Cable Installation MPO to MPO Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.6.5
MPO Trunk Cable Installation MPO to LC Blade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Installation Instructions
© 2016 CommScope. All Rights Reserved.
Quareo
24749-A
Page
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Quareo 4000 and is the answer not in the manual?

Questions and answers

Summary of Contents for CommScope Quareo 4000

  • Page 1: Table Of Contents

    TECHNICAL ASSISTANCE..............24 300001739168 Rev B Page 1 www.commscope.com © 2016 CommScope. All Rights Reserved.
  • Page 2: Introduction

    Ethernet port. This document describes the installation of the chassis in a typical rack installation. Trademark Information CommScope (logo), CommScope, and Quareo are trademarks Admonishments Important safety admonishments are used throughout this manual to warn of possible hazards to persons or equipment.
  • Page 3: Specifications

    1. Inspect the exterior of the shipping container(s) for evidence of rough handling that may have damaged the components in the container. 2. Unpack each container while carefully checking the contents for damage and verify with the packing slip. Page 3 © 2016 CommScope. All Rights Reserved.
  • Page 4: Chassis Installation

    ADCP-92-309 • Issue 4 • July 2016 3. If damage is found or parts are missing, file a claim with the commercial carrier and notify CommScope Customer Service. Save the damaged cartons for inspection by the carrier. 4. Refer to Section 4 Technical Assistance if you need to contact CommScope.
  • Page 5 Caution: When mounting equipment in the rack make sure mechanical loading is even to avoid a hazardous condition, such as loading heavy equipment in the rack unevenly. The rack should safely support the combined weight of all equipment it supports. Page 5 © 2016 CommScope. All Rights Reserved.
  • Page 6: Quareo Cross-Connect Solution Installation

    In the Quareo cross-connect solution frame there are eight spaces for mounting network chassis. Consider them to be numbered one through eight starting at the top, see Figure 24732-A FRONT VIEW Figure 2. Quareo Cross-Connect Solution Frame Page 6 © 2016 CommScope. All Rights Reserved.
  • Page 7: Grounding Chassis

    3. To assure proper operation the chassis should be connected to a good earth ground. There must be no switching or disconnecting devices in the grounding circuit conductor between the power source and the point of connection to the grounding electrode conductor. Page 7 © 2016 CommScope. All Rights Reserved.
  • Page 8: Power Cabling

    (AUX power) is present. If power is not provided through the AUX port the controller assumes a PoE switch is the voltage source. During the AUX power application to the controller the Page 8 © 2016 CommScope. All Rights Reserved.
  • Page 9: Aux Power

    Remove the ferrule dust cap from one of the patch cord connectors and then clean the connector as specified in the Optical Fiber Connector Wet and Dry Cleaning Instructions (ADCP-90-159) or by locally approved procedures. Page 9 © 2016 CommScope. All Rights Reserved.
  • Page 10 Caution: If blades are in one of the detent positions when fiber connections are made, make certain that there is enough slack in the cable so that when blade is pushed in fiber bend radius is not compromised. Page 10 © 2016 CommScope. All Rights Reserved.
  • Page 11: Cable Installation

    Use the following procedure to install cable when blade has the cable tie clip: 1. Locate the cable entry location that is specified for cable installation as shown in Figure Page 11 © 2016 CommScope. All Rights Reserved.
  • Page 12 Before connecting MPO connectors to MPO to MPO adapters pull blade out to the second detent. 7. Use Mille-Ties to secure cables to cable tie clip. See Figure 8. Use Mille-Ties to bundle cables together as necessary. 8. Close blade after installing Mille-Ties. Page 12 © 2016 CommScope. All Rights Reserved.
  • Page 13: Lc Array Cable Installation

    5. Slide fiber fanout onto posts on chassis. After installing the last fiber fanout slide a fanout retainer over each post. 6. Use Mille-Ties to secure cables to cable tie clip. See Figure 9. Use Mille-Ties to bundle cables together as necessary. 7. Close blade after installing Mille-Ties. Page 13 © 2016 CommScope. All Rights Reserved.
  • Page 14: Lc Trunk Cable Installation Lc To Lc Blade

    2. Route cables to chassis securing cables and breakout to rack per local practices. 3. Assemble grommets and cable clamps on fiber cables as shown in Figure Page 14 © 2016 CommScope. All Rights Reserved.
  • Page 15 More than one grommet may be needed to secure cables in the clamp. 5. Remove cable covers from blades by sliding towards the rear of the blade and lifting out of the retaining slot. See Figure FIBER COVER 24914-A Figure 11. Fiber Cover Removal Page 15 © 2016 CommScope. All Rights Reserved.
  • Page 16 6. Place fanouts into retaining positions on rear of blade. Secure fanouts to blade with clips provided. See Figure 12 for clip installation. FIBER BREAKOUT FANOUT CLIP FANOUT 24916-A 8-INCH (20 CM) SERVICE LOOP CABLE CLAMPS MILLE-TIES Figure 12. Fanout Clip Installation Page 16 © 2016 CommScope. All Rights Reserved.
  • Page 17 Insert connector into the adapter. e. While holding fibers in place slide blade cover into slot. Pull cover to the front of the blade and latch in place. See Figure 9. Close blade. Page 17 © 2016 CommScope. All Rights Reserved.
  • Page 18: Mpo Trunk Cable Installation Mpo To Mpo Blade

    4. Cable clamps and several grommets are provided with the cable clamp kit for securing cables to the chassis. More than one grommet may be needed to secure cables in the clamp. Page 18 © 2016 CommScope. All Rights Reserved.
  • Page 19 5. Connect cables to the back of the adapters: a. Pull blade out to the second detent. b. Remove dust cap, inspect, and clean MPO connector per ADCP-96-150 instructions before terminating. c. Insert connectors into the adapters. Page 19 © 2016 CommScope. All Rights Reserved.
  • Page 20 Route fibers between lances at the rear of the blade. Use a Millie-Tie to secure fibers to the blade. See Figure FIBER BREAKOUT 24918-A MILLE-TIES 8-INCH (20 CM) CABLE SERVICE CLAMP LOOP 8 MPO CABLES Figure 16. Cable Placement Page 20 © 2016 CommScope. All Rights Reserved.
  • Page 21 17. Tighten compression fitting screws to secure cables at the cable entry location. Use a Millie-Tie to bundle fibers together. FIBER BREAKOUT 24919-A MILLE-TIES 8-INCH (20 CM) CABLE SERVICE CLAMP LOOP 8 MPO CABLES Figure 17. Cable Installation Page 21 © 2016 CommScope. All Rights Reserved.
  • Page 22: Mpo Trunk Cable Installation Mpo To Lc Blade

    1.5 in. (3.81 cm). 5. Connect cables to the back of the adapters: 6. Remove dust cap, inspect, and clean MPO connector per ADCP-96-150 instructions before terminating. Page 22 © 2016 CommScope. All Rights Reserved.
  • Page 23 CABLE CLAMPS MILLE-TIES Figure 19. Cable Installation Complete chassis installation by installing controllers, chassis status board, and connecting Ethernet port to the chassis controller. Refer to appropriate installation instructions for complete details. Page 23 © 2016 CommScope. All Rights Reserved.
  • Page 24: Technical Assistance

    ADCP-92-309 • Issue 4 • July 2016 4 TECHNICAL ASSISTANCE Contact the Technical Assistance Center (TAC) for technical question. Call 800.830.5056 or send an email to TAC.Americas@commscope.com. Page 24...
  • Page 25 ADCP-92-309 • Issue 4 • July 2016 Page 25 © 2016 CommScope. All Rights Reserved.