AC Tech SCF series Installation And Operation Manual page 34

Variable speed ac motor drives
Hide thumbs Also See for SCF series:
Table of Contents

Advertisement

NO.
PARAMETER NAME
27
BASE FREQUENCY
28
FIXED BOOST
29
ACCEL BOOST
30
SLIP COMPENSATION
31-37
PRESET SPEEDS
38
SKIP BANDWIDTH
39
SPEED SCALING
40
FREQUENCY SCALING
41
LOAD SCALING
42
ACCEL / DECEL #2
43
SERIAL ADDRESS
44
PASSWORD
47
CLEAR HISTORY
48
PROGRAM
SELECTION
50
FAULT HISTORY
51
SOFTWARE CODE
52
DC BUS VOLTAGE
53
MOTOR VOLTAGE
54
LOAD
55
0-10 VDC INPUT
56
4-20 mA INPUT
57
TB STRIP STATUS
58
KEYPAD STATUS
59
TB-30 OUTPUT
60
TB-31 OUTPUT
NOTE 1:
Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.
NOTE 4:
Maximum setting is 1300.0 Hz (factory default is 999.9) on drives with High Output Frequency option.
Consult the factory.
PARAMETER MENU (CONT'D)
RANGE OF ADJUSTMENT
25.0 - 500.0 Hz (NOTE 4)
0.0 - 30.0 %
0.0 - 20.0 %
0.0 - 5.0 %
0.0 - MAXIMUM FREQUENCY
0.0 - 10.0 Hz
0.0 - 6500.0
3.0 - 2000.0 Hz
10 - 200 %
0.1 - 3600.0 SEC
1 - 247
000 - 999
MAINTAIN (01), CLEAR (02)
USER SETTINGS (01), OEM SETTINGS (02),
RESET OEM (03), RESET 60 (04),
RESET 50 (05), TRANSLATE (06)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
(VIEW-ONLY)
31
FACTORY
DEFAULT
(NOTE 1)
60.0 Hz
1.0 %
0.0 %
0.0 %
0.0 Hz
0.0 Hz
0.0
60.0 Hz
200 %
20.0 SEC
1
225
MAINTAIN (01)
USER
SETTINGS (01)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)
(N/A)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents