Fisher 2506 Instruction Manual

Fisher 2506 Instruction Manual

Receiver/controllers
Hide thumbs Also See for 2506:

Advertisement

Instruction Manual
D200129X012
Fisher
2506 and 2516 Receiver/Controllers
Contents
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
2500 Controller/Transmitter and
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bellows Replacement
Changing Proportional or Reset Valve
Parts Ordering
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Receiver/Controller Common Parts
Anti-Reset Windup Valve for 2516F Only
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . . . . . .
. . . . . . .
Figure 1. Fisher 2506 Receiver-Controller
2
2
2
2
4
5
5
6
6
7
8
W4687
.
9
11
12
12
12
12
13
Figure 2. Fisher 2516 Receiver-Controller
13
14
14
15
15
15
15
16
17
17
18
W4688
19
19
20
21
21
21
22
22
22
23
23
23
26
2506/2516 Receiver/Controller
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . .
June 2017
26
27
27
27
27
27
27

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 2506 and is the answer not in the manual?

Questions and answers

Summary of Contents for Fisher 2506

  • Page 1: Table Of Contents

    ™ Contents Figure 1. Fisher 2506 Receiver‐Controller Introduction ....... . .
  • Page 2: Introduction

    Emerson sales office or Local Business Partner. Do not install, operate, or maintain a 2506/2516 receiver/controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury or property damage, it is important to carefully read, understand, and follow all contents of this quick start guide, including all safety cautions and warnings.
  • Page 3 A maximum 40 micrometer particle size in the air direct or reverse (R) action system is acceptable. Further filtration down to 5 2516: A 2506 that also provides proportional‐plus- micrometer particle size is recommended. Lubricant reset control content is not to exceed 1 ppm weight (w/w) or 2516F: A 2516 that also provides anti‐reset windup...
  • Page 4: Educational Services

    5. If air consumption is desired in normal m /hr at 0°C and 1.01325 bar, multiply scfh by 0.0268. Educational Services For information on available courses for 2506 or 2516 receiver/controllers as well as a variety of other products, contact: Emerson Automation Solutions...
  • Page 5: Installation

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 Installation WARNING To avoid personal injury or property damage resulting from the sudden release of pressure: D Always wear protective clothing, gloves, and eyewear when performing any installation procedures to avoid personal injury. D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
  • Page 6: Actuator Yoke Mounting

    Instruction Manual 2506/2516 Receiver/Controller June 2017 D200129X012 Actuator Yoke Mounting See figure 4 for a typical mounting plate. Key numbers are shown in figure 5. 1. Locate the mounting plate (key 164, figure 5). Select appropriate mounting holes in the mounting plate for the receiver/controller.
  • Page 7: Actuator Diaphragm Case Mounting

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 Figure 6. Wall Mounting SPACER (KEY 78) (7.62) MOUNTING PLATE (KEY 164) CAP SCREW AND LOCKWASHER (KEYS 39 AND 83) SPACER (KEY 174) AD4913‐H SIDE VIEW A3847‐1 (INCH) 1. Install lock washers (key 83) on the cap screws (key 39). Then, insert the cap screws through the mounting plate from “back to front”.
  • Page 8: Pipestand Mounting

    3. Locate the receiver/controller mounting position on the horizontal edge of the diaphragm case. A typical Fisher diaphragm actuator features upper and lower diaphragm casings held together with hex head cap screws and hex nuts.
  • Page 9: Controller/Transmitter And 2506/2516 Receiver/Controller Mounting

    If the receiver/controller is ordered separately for use with a 2500 controller/transmitter, it may not have the required mounting parts. If mounting parts are required, consult the parts list under the specific mounting application. See figure 9 for key number locations. Figure 9. Fisher 2500 Controller‐Transmitter and 2506/2516 Receiver‐Controller Mounting (9.25) TUBING...
  • Page 10 Instruction Manual 2506/2516 Receiver/Controller June 2017 D200129X012 2. Install lock washers (key 83) on the cap screws (key 48). Then, insert the cap screws through the mounting plate from “back to front”. Thread the cap screws into the mounting holes in the controller/transmitter.
  • Page 11: Connections

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 Figure 11. Typical Transmitter and Receiver Installation with an Indicator and Remote Set Point Connection INDICATOR 2500 CONTROLLER/ CONTROLLER/ TRANSMITTER TRANSMITTER SUPPLY SUPPLY PANEL LOADER REMOTE SET POINT ADJUSTMENT CENTRALIZED CONTROL PANEL CONTROLLER OUTPUT PIPING...
  • Page 12: Supply Connection

    3. It is recommended that supply pressure pass through a filter/regulator combination such as a Fisher 67CFR. See table 3 for recommended supply pressures to the receiver/controller.
  • Page 13: Remote Set Point Connection

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 or hazardous gas. The case and cover assembly does not form a gas‐tight seal and flammable or hazardous gas could leak from this unit. Therefore, if the receiver/controller unit is enclosed, install a remote vent line to remove part of the exhaust gas to a properly ventilated area.
  • Page 14: Adjustments

    2. Turn on the supply pressure to the receiver/controller. D To make the proper level or output pressure setting for a 2506 receiver/controller, go to step 3. To make the proper level or output pressure setting for a 2516 receiver/controller, go to step 9.
  • Page 15: Remote Set Point Adjustment

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 To lower level or decrease density, rotate the knob in the opposite direction. The INCREASE OUTPUT PRESSURE or RAISE LEVEL dial is graduated (in percent) to show approximate indications of the receiver/controller set point. When making adjustments, do not rely only on the dial setting.
  • Page 16: Calibration

    One way to obtain an open loop is to disconnect the controller output signal line and install a pressure gauge. Note When calibrating a combined controller arrangement such as the 2500 with the 2506 or 2516 (figure 9), calibrate the 2500 controller/ transmitter first. For a direct action receiver/controller: 1.
  • Page 17: Principle Of Operation

    Principle of Operation The 2506/2516 uses a basic pressure balance relay system. The relay is connected so that supply pressure is fed to the inlet side of the relay valve and the fixed restriction. From this restriction, the air pressure bleeds into the relay chamber on one side of the large diaphragm and also to the nozzle.
  • Page 18: 2516, 2516F Receiver/Controllers

    The action of a proportional‐plus‐reset controller (figure 13) is similar to that of a proportional controller except that feedback from the controller output pressure is piped to a reset bellows as well as to the proportional bellows. Figure 13. Fisher 2516 and 2516F Direct Action Receiver‐Controller Schematic TRANSMITTER INPUT...
  • Page 19: Maintenance

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 The 2516F receiver/controller also features an anti‐reset windup valve. This valve provides differential pressure relief to prevent proportional pressure from exceeding reset pressure by more than a set value. The proportional valve output pressure registers on one side of the diaphragm chamber and the reset valve output pressure registers on the other side diaphragm.
  • Page 20: Troubleshooting

    D The bellows assembly on the left provides either direct or reverse action. The receiver/controller (2506 or 2516) can be changed between direct and reverse action by repositioning the switch plate (key 132) on the left. Direct action (D) is when increasing transmitter input pressure increases receiver/controller output pressure.
  • Page 21: Testing Relay Deadband

    Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 Table 5.Troubleshooting Chart (continued) Fault Possible Cause Check Correction 4. Receiver/controller remains 4.1 Supply or output pressure 4.1 Insure the pressure gauges are 4.1 Replace pressure gauges. at full or zero output pressure.
  • Page 22: Changing The Relay

    Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Automation Solutions should not, under any circumstances be used in any Fisher instrument. The use of components not manufacture by Emerson Automation Solutions may void your warranty, might adversely affect the performance of the instrument, and could cause...
  • Page 23: Parts Kits

       tapped vent for vent line)   High Temperature RRELAYX0H22   2 Controller cover, die cast   3 Door handle, steel pl 2506/2516 Controller Cover Gasket Kit  Contains qty. 5 cover gaskets, key 21 R2506CVR012   4 Door handle shaft, stainless steel  (not shown)   5 Machine screw, steel pl   6...
  • Page 24 Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 Description Description  91 Reset restriction valve assembly  31 Nut, brass (2 req'd)  2516   Standard temperature  32 Flapper, K93602 nickel alloy   High temperature  34 Relay assembly  2516F  Standard temperature   Standard temperature  High temperature  96 Bellows screw (4 req'd)  35...
  • Page 25 Instruction Manual 2506/2516 Receiver/Controller D200129X012 June 2017 Figure 14. Fisher 2506 and 2516 Receiver‐Controller Assemblies 2506 ASSEMBLY SETPOINT ADJUSTMENT 30A8956‐B USE W/THREADED CASE VENT RESET VALVE ADJUSTMENT PROPORTIONAL BAND VALVE VIEW A ADJUSTMENT WITH SWITCH PLATE REMOVED C0670‐2 2516 ASSEMBLY...
  • Page 26: 2516F Reset And Anti-Reset Windup

    Spring seat, aluminum Differential relief valve Machine screw, stainless steel (4 req'd) Machine screw, stainless steel (2 req'd) Figure 15. Fisher 2516F Anti‐Reset Windup Valve Figure 16. Fisher 2516F Reset and Anti‐Reset Windup Assembly Valve Assembly RESET VALVE ADJUSTMENT ADJUSTMENT...
  • Page 27: Mounting Parts

    Mounting plate, steel pl  83 Lock washer (4 req'd) Mounting plate, steel pl Spacer, (2 req'd) Regulator mounting on 2506, 2516. With separate supply sources Regulator mounting and separate regulators Nipple, to join regulator to Nipple, to join regulator to receiver/controller  supply connection...
  • Page 28: Www.fisher.com

    Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user. Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co.

This manual is also suitable for:

2516

Table of Contents