Damper Installation - Dunkirk DXL-50 Installation, Operation & Maintenance Manual

Dxl series ii cast iron gas fired boilers for forced hot water
Table of Contents

Advertisement

9= VENT
DAMPER
INSTALLATION
& INSTRUCTIONS
DAMPER
INSTALLATION
NOTE: Referto Figure 10 forsteps i-6.
Figure
11
- Damper
Motor
Wiring
DAMPER INSTRUCTIONS
Figure
12
- Vent
Damper
Placement
\
Vent Damper
Vent Outlet
Damper Motor
"iOF
V#ATk
H_ At_
_k
1.
Place vent damper on or as close to vent outlet of
boiler as possible. See Figure 12,
2.
Remove vent damper motor cover.
3.
Feed damper wire harness connector through bracket
hole on damper motor frame.
4.
Tighten Iocknut onto damper wire harness connector.
5.
Plug damper connector into socket on damper motor
frame.
6.
Replace damper motor cover and wire damper. See
Figure 11.
1.
Verify only boiler is serviced by vent damper, See
Figure 12.
2.
Clearance of not less than 6 inches between vent
damper and combustible
material must be maintained,
Additional
clearance should be allowed for service of
vent damper,
3.
Vent damper must be in the open position when
appliance main burners are operating,
4.
Vent damper position indicator must be in a visible
location following installation,
5.
The thermostat's
heat anticipator
must be adjusted to
match the total current draw of all controls associated
with boiler during heating cycle,