To connect 600 mm (24 in.) units:
•
On each unit, connect one plug on the CAT5 cable to ETH-2 on the rear of the display, and the
other to the network switch, Figure 9.14 below.
Figure 9.14 Connecting 600 mm (24 in.) units
9.2.5 Wiring Cooling Units with Wall-mount Displays
NOTE: Cooling units are factory-wired for stand-alone operation. Do not connect the U2U network
cabling before setting the U2U network configuration/groups. Network communication conflicts and
unreliable display readings will result.
NOTE: Before you begin, refer to Preparing for U2U Group Set-up, and Configuring U2U Network
Settings, in the "Liebert® iCOM™ User Manual," included with your system documentation.
Large, wall-mount displays may be used to remotely configure, control and monitor all cooling units
connected on the U2U network.
•
Each display requires 120 VAC or 230 VAC input power.
•
An AC-adapter wall plug is factory-supplied.
Vertiv | Liebert CRV Installer/User Guide |
ITEM
DESCRIPTION
1
Touchscreen (rear view)
2
Ethernet cable (field-supplied)
3
Ethernet cable
4
iCOM I/O board
5
Network switch (field-supplied)
6
to ETH-2 on rear of other cooling-unit touchscreens
108