Wiring Cooling Units With Wall-Mount Displays - Vertiv Liebert CRV Installer/User Manual

Row-based cooling system
Hide thumbs Also See for Liebert CRV:
Table of Contents

Advertisement

To connect 600 mm (24 in.) units:
On each unit, connect one plug on the CAT5 cable to ETH-2 on the rear of the display, and the
other to the network switch, Figure 9.14 below.
Figure 9.14 Connecting 600 mm (24 in.) units

9.2.5 Wiring Cooling Units with Wall-mount Displays

NOTE: Cooling units are factory-wired for stand-alone operation. Do not connect the U2U network
cabling before setting the U2U network configuration/groups. Network communication conflicts and
unreliable display readings will result.
NOTE: Before you begin, refer to Preparing for U2U Group Set-up, and Configuring U2U Network
Settings, in the "Liebert® iCOM™ User Manual," included with your system documentation.
Large, wall-mount displays may be used to remotely configure, control and monitor all cooling units
connected on the U2U network.
Each display requires 120 VAC or 230 VAC input power.
An AC-adapter wall plug is factory-supplied.
Vertiv | Liebert CRV Installer/User Guide |
ITEM
DESCRIPTION
1
Touchscreen (rear view)
2
Ethernet cable (field-supplied)
3
Ethernet cable
4
iCOM I/O board
5
Network switch (field-supplied)
6
to ETH-2 on rear of other cooling-unit touchscreens
108