Ceiling Cassette Type - LG AMNH076LQL0 Service Manual

Multi type air conditioner
Hide thumbs Also See for AMNH076LQL0:
Table of Contents

Advertisement

Installation

Ceiling Cassette Type

1) PRECAUTIONS IN TEST RUN
• The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
For test run, carry out the cooling operation first even during winter season. If heating operation is
Caution
carried out first, it leads to the trouble of compressor.
Carry out the test run more than 5 minutes without stopping.
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the room temperature checking button and down timer button for 3 sec-
onds at the same time.
• To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured data, etc.
• Measuring data are room temperature, outside temperature, suction temperature, blow out temperature,
air velocity, air volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping
temperature.
• As to the structure and appearance, check following items.
Is the circulation of air adequate?
Is the drainage OK?
Is the heat insulation complete
(refrigerant and drain piping)?
Is there any leakage of refrigerant?
5. Branch Distributor
PRECAUTIONS FOR SELECTING THE LOCATION
The BD unit is for indoor use. Install in a location such as above a ceiling or behind a wall in accordance with the
following conditions:
• That the unit is fully supported, and is in a location with little or no vibration.
• That the refrigerant pipes for the indoor and outdoor units can be repaired with ease, and that the units are
placed well within the distance from each other allowed by the pipe length.
• That there is nothing nearby that produces heat or steam(gas).
• When installing, that there is enough carity for servicing the unit.
• Do not install in location that is hot or humid for long periods of time.
• A well-ventilated area.
• Do not install near bedrooms. The sound of refrigerant flowing through the piping may sometimes be audible.
For restrictions on installation, refer to "INSTALLATION".
84 Multi type Air Conditioner
Does the romote controller works properly?
Is there any error on wiring?
Aren't terminal screws loosened?
M4......118N.cm{12kgf.cm} M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm} M8......588N.cm{60kgf.cm}