ABB
Grid Automation Controller
COM600
Product version: 4.0
Table 5. Optional PCI extensions
Description
Serial interfaces
1)
Ethernet interfaces
2)
1) Operating temperature 0° C - +55° C
2) Operating temperature 0° C - +55° C
Table 6. Inspection of mechanical structure
Description
Markings and mechanical structure According to IEC 60255-1, -5
Degree of protection by enclosure
Clearance and creepage distances
Table 7. Power supply and module tests
Description
Auxiliary voltage
Aux. voltage interruptions
Ripple in auxiliary DC voltage
Power consumption
Table 8. Insulation tests
Description
Dielectric test
Impulse voltage test
Insulation resistance
Protective bonding impedance
Value
8 x RS-232/485 serial interfaces
2 x 10BASE-T/100BASE-TX/1000BASE-T RJ-45
interfaces
Reference
According to IEC 60529
According to IEC 60255-5
Reference
According to IEC 60255-1
According to IEC 60255-11
According to IEC 60255-11 15%, f = 2 x fn
According to CE EN 61010
Reference
According to IEC 60255-5
2 kV, 50 Hz for 1 minute
According to IEC 60255-5
5 kV, 1.2/50 μs, 0.5 J
According to IEC 60255-5
>100 MΩ, 500 Vdc
According to IEC 60255-27
<0.1 Ω.
1MRS756764 D