Venting Clearances - Navien NR-180 Installation Manual

Hide thumbs Also See for NR-180:
Table of Contents

Advertisement

Navien Gas Water Heater Installation

█ Venting Clearances:

All clearance requirements are in accordance with ANSI Z21.10.3 and the
National Fuel Gas Code, ANSI Z223.1 / NFPA 54 and CAN/CGA B149.1
National Gas and Propane Installation Code.
ANSI Z223.1 / NFPA 54 CAN/CGA B149.1 National Gas and Propane Installation Code.
Clearance To:
A
Above grade, veranda, porch, deck or balcony
B
Window or door that may be opened
C
Permanently closed window
Vertical clearance to ventilated soffit located
D
above the terminal within a horizontal distance
of 2 feet from the center of the terminal
E
Unventilated soffit
F
Outside corner
G
Inside corner
Each side of center line extended above
H
meter/regulator assembly
I
Service regulator vent outlet
Non-mechanical air supply inlet or combustion
J
air inlet to any other appliance
K
Mechanical air supply inlet
Above paved sidewalk or paved driveway
L
located on public property
M
Under veranda, porch, deck, or balcony
US Direct Vent
Canada Direct Vent
Indoor Installation
Indoor Installation
1'
1'
1'
3'
*
*
*
*
*
*
*
*
*
*
3' within a height
15'above
*
meter/regulator
assembly
*
3'
1'
3'
3' above if within 10'
6'
horizontally
*
7'
*
1'
29