FOR COMPLETE CHARGING DETAILS, REFER TO THE OUTDOOR UNIT INSTALLATION INSTRUCTION.
AIRFLOW CHECK - Both airflow and refrigerant charge must be monitored
for a proper system set‐up. It may be necessary to alternately check and
adjust the airflow and the refrigerant charge.
NOTE - Be sure that filters and indoor and outdoor coils are clean before testing.
To determine temperature drop across indoor coil (Delta-T), measure the entering air dry
bulb (DB) and wet bulb (WB) temperatures at the indoor coil. Find Delta-T in table 1. Measure
coil's leaving air DB and subtract that value from entering air DB. The measured difference
should be within +3ºF (+1.8ºC) of table value; if too low, decrease the indoor fan speed (refer
to indoor unit for information). If the Delta-T is too high, increase the indoor fan speed. Repeat
charging procedure and Delta-T (air flow adjustment) procedure until both are correct.
Example:
assume entering air DB - 72, WB - 64, leaving DB - 53. Therefore, Delta-T should
be 15 (per table); delta across coil is 72 - 53 or 19 (which is 4ºF higher than table value); action
necessary: increase fan speed.
Table 1. Evaporator Coil Delta-T
Dry bulb
80 24 24 24 23 23 22 22 22 20 19 18 17 16 15
temperature 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14
of air
76 22 22 22 21 21 20 19 19 18 17 16 15 14 13
entering
74 21 21 21 20 19 19 18 17 16 16 15 14 13 12
indoor
72 20 20 19 18 17 17 16 15 15 14 13 12 11 10
coil (ºF)
70 19 19 18 18 17 17 16 15 15 14 13 12 11 10
ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70
[
Wet bulb temperature of air entering indoor coil
Table 2. Superheat (SH) Value
40 15 18 20 23 26 29 32 34 38 41 43 46 48 51
45 13 16 18 21 24 27 30 33 36 39 41 44 46 49
50 11 14 16 19 22 25 28 31 34 37 39 42 44 47
Dry bulb
55
9
12 14 17 20 23 27 30 33 36 38 40 42 44
temperature 66
7
10 12 15 18 21 24 27 30 33 35 38 40 43
of ambient
65
6
10 13 16 19 21 24 27 30 33 36 38 41
air entering
70
7
10 13 16 19 21 24 27 30 33 36 39
outdoor
75
6
unit (ºF)
80
85
90
95
100 ‐
105 ‐
110 ‐
115 ‐
ºF 50 52 54 56 58 60 62 64 66 68 70 72 74 76
[
Wet bulb temperature of air entering indoor coil
07/09
*2P0709*
RFC System - +5ºF
9
12 15 18 21 24 28 31 34 37
5
8
12 15 18 21 25 28 31 35
8
11 15 19 22 26 30 33
5
9
13 16 20 24 27 31
6
10 14 18 22 25 29
8
12 16 21 24 28
5
9
13 17 22 26
6
11 15 20 25
8
14 18 24
CHARGING INFORMATION
Size
Table 3. Normal Operating Pressures
2
°F(°C)
TXV System - Liquid Line (+10 psig) / Vapor Line (+5 psig)
65 (18)
233 / 132
70 (21)
251 / 133
75 (24)
265 / 133
80 (27)
292 / 135
85 (29)
314 / 136
90 (32)
338 / 137
95 (35)
362 / 138
100 (38)
388 / 140
105 (41)
415 / 141
110 (43)
444 / 142
115 (45)
475 / 143
2
°F(°C)
Fixed Orifice (RFC) - Liquid Line (+10 psig) / Vapor Line (+5 psig)
65 (18)
233 / 121
70 (21)
250 / 124
]
75 (24)
270 / 128
80 (27)
291 / 131
85 (29)
313 / 134
90 (32)
335 / 136
95 (35)
359 / 138
100 (38)
383 / 140
105 (41)
409 / 142
110 (43)
436 / 145
115 (46)
464 / 147
Table 4. Approach (APP) Values
All
4 (2.2)
Table 5. Subcooling (SC) Values
All
10 (5.6)
1 Typical pressures; indoor evaporator match up, indoor air quantity, and evaporator load will cause
the pressures to vary.
2 Temperature of air entering outside coil.
3 Approach = Liquid Line Temp. minus Outdoor Ambient Temperature
4 Subcooling = Saturation Temp. minus Liquid Line Temp Temperature
]
-18
-24
-30
-36
1
244 / 137
248 / 127
263 / 135
263 / 138
263 / 131
281 / 138
285 / 139
284 / 132
302 / 140
307 / 140
307 / 134
325 / 142
329 / 141
330 / 135
349 / 142
354 / 142
355 / 136
375 / 143
379 / 143
380 / 137
404 / 144
404 / 144
407 / 138
433 / 145
438 / 145
434 / 139
462 / 147
464 / 147
465 / 141
494 / 149
495 / 148
497 / 142
527 / 150
246 / 126
245 / 123
261 / 134
265 / 129
265 / 126
281 / 136
286 / 132
286 / 129
301 / 138
307 /135
308 / 132
324 / 140
330 / 137
331 / 135
346 / 142
353 / 140
355 / 138
371 / 144
378 / 142
380 / 140
396 / 146
402 / 143
405 / 142
422 / 148
428 / 145
431 / 144
448 / 150
456 / 147
458 / 146
477 / 151
486 / 149
487 / 148
506 / 153
3
-
TXV System - ºF (ºC) +1ºF (0.5ºC)
8 (4.4)
8 (4.4)
11 (6.1)
4
-
TXV System - ºF (ºC) +1ºF (0.5ºC)
10 (5.6)
9 (5.0)
12 (6.7)
*P580052-01*
-42
-48
-60
238 / 132
235 / 132
241 / 130
262 / 133
254 / 132
260 / 130
280 / 134
276 / 134
280 / 132
301 / 136
298 / 134
299 / 134
327 / 137
323 / 135
321 / 135
353 / 138
350 / 137
344 / 134
377 / 140
377 / 138
371 / 135
404 / 141
406 / 140
400 / 137
435 / 142
430 / 141
428 / 139
465 / 143
464 / 142
458 / 141
499 / 144
495 / 143
484 / 142
246 / 126
247 / 125
248 / 124
263 / 128
266 / 128
266 / 126
284 / 131
286 / 131
288 / 130
305 / 133
307 / 133
309 / 133
327 / 135
329 / 135
330 / 135
350 / 138
353 / 138
354 / 138
374 / 140
377 / 140
377 / 140
399 / 142
403 / 142
406 / 142
424 / 144
428 / 144
431 / 144
452 / 146
455 / 146
457 / 146
481 / 148
483 / 147
484 / 148
9 (5.0)
8 (4.4)
9 (5.0)
9 (5.0)
9 (5.0)
7 (3.9)
580052-01