Unscheduled Removals - Teledyne 7639-27 Maintenance Manual

Lt-valve-regulated lead-acid batteries
Table of Contents

Advertisement

7.1
Unscheduled removals may be required when the battery has been inadvertently
discharged or has a premature failure. Recharging the battery using Constant Potential
method described in Section 5.2 should be attempted. Perform a capacity check as
outlined in Section 6.2. If the battery fails to provide specified capacity as noted in Table
2, Appendix A, it should be rejected.
Q01-4000
COMPONENT MAINTENANCE MANUAL

7. UNSCHEDULED REMOVALS

Rev G
Page 17 of 28
Teledyne Battery Products

Advertisement