Stratus ftServer 3300, 5600, and 6600: Site Planning Guide Stratus Technologies R553-01...
Page 2
Stratus, the Stratus logo, ftServer, Continuum, Continuous Processing, StrataLINK, and StrataNET are registered trademarks of Stratus Technologies Bermuda, Ltd. The Stratus Technologies logo, the ftServer logo, Stratus 24 x 7 with design, The World’s Most Reliable Servers, The World’s Most Reliable Server Technologies, ActiveService, ftGateway, ftMemory, ftMessaging, ftStorage, Selectable Availability, XA/R, SQL/2000, and The Availability Company are trademarks of Stratus Technologies Bermuda, Ltd.
Site Planning for Fault-Tolerant Systems Site Planning Checklist System Documentation 2. Cabinet and Monitor Requirements Rack Requirements Cabinet Requirements for ftServer 3300, 5600, and 6600 Systems Additional Cabinet Requirements for ftServer 6600 Systems 2-2 Additional Cabinet Requirements for ftServer 3300 and 5600 Systems Monitor Requirements 3.
Page 4
APC UPS Models for Use with ftServer 6600 Systems APC UPS Models for Use with a Single ftServer 5600 System APC UPS Models for Use with Multiple ftServer 3300 and 5600 Systems APC UPS Models for Use with a Single ftServer 3300...
Page 5
Contents Appendix B. Specifications of Peripheral and Storage Components B-1 D540 Storage Enclosure Specifications V128 LCD Monitors Specifications V129 LCD Monitor Specifications V115 Keyboard Specifications AAP41105 PDU Specifications AAP41104 PDU Specifications B-10 AK470 KVM Switch Specifications B-12 AA000400 USB Floppy Disk Drive Specifications B-14 T521 and T522 Tape Drive Enclosure Specifications B-15...
Page 6
Figure A-6. Pedestal ftServer 3300 System - Rear View A-11 Figure A-7. Rack-Mountable ftServer 3300 System - Front View A-13 Figure A-8. Rack-Mountable ftServer 3300 System - Rear View A-14 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 8
4-11 Table 4-16. ftServer 3300 System Power Cords: 100–127V and 50–60 Hz 4-11 Table 4-17. ftServer 3300 System Power Cords: 200–240V and 50 Hz 4-11 Table 4-18. ftServer 3300 System Power Cords: 200–240V and 50–60 Hz 4-12 Table 4-19. ftServer 3300 Systems: Power Cords to Connect Systems...
Page 9
APC Symmetra Models for PDUs and Multiple ftServer 5600 Systems Table 5-7. APC UPS Models for a Single Rack-Mountable ftServer 3300 System Table 5-8. APC UPS Models for a Single Pedestal ftServer 3300 System Table 6-1. Customer-Supplied Ethernet Cables Table 7-1. Component Power Requirements Table 7-2.
Page 10
Tables Table D-4. Noise Standards Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Autoloader, which can no longer be purchased. • Describes new uninterruptible power supply (UPS) models available from APC for use with a single ftServer 3300 system and for use with a single ftServer 5600 system. • Directs you to consider the requirements for the U574 Dual-Port Fiber Gigabit Ethernet Adapters and U575 Dual-Port Copper Gigabit Ethernet Adapters.
If you have a technical question about ftServer system hardware or software, try these online resources first: • Online support from Stratus Customer Service. You can find the latest technical information about an ftServer system through online product support at the Stratus Technical Support Web site: http://www.stratus.com/support/technics.htm...
Page 13
If you are unable to resolve your questions with the help available at these online sites, and the ftServer system is covered by a service agreement, please contact the Stratus Customer Assistance Center (CAC) or your authorized Stratus service representative.
Page 14
Preface Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Chapter 1 Welcome to Site Planning for ftServer Systems For an overview of the information you need to know and the tasks you need to perform to prepare a site for ftServer systems, see: • “Site Planning Overview” on page 1-2 •...
• Purchasing an appropriate cabinet and monitor If you do not purchase a cabinet from Stratus, ensure that the cabinet you plan to use meets the system’s requirements. If you do not purchase a monitor from Stratus, make sure that the monitor you plan to use meets the system’s requirements.
• ftServer systems can connect to the Stratus ActiveService Network (ASN). Connecting a system to the ASN allows the CAC or your authorized Stratus service representative to remotely diagnose, troubleshoot, and resolve problems online. To enable connectivity to the Stratus ActiveService Network (ASN), which allows...
Referring to the information in this document, answer the following questions: Planning for ActiveService Network Connectivity Will your system use ftServer Access Adapters to connect to the Stratus ASN? If your system uses ftServer Access Adapters, will you connect the adapters to a...
Page 19
U574 Dual-Port Fiber Gigabit Ethernet Adapter U575 Dual-Port Copper Gigabit Ethernet Adapter Will you supply your own monitor or will you use a monitor supplied by Stratus? Is the monitor rack-mountable or do you need to provide a table or desk? N O T E Use the USB keyboard and mouse supplied by Stratus.
Page 20
If you have any questions about the number and types of components, contact your Stratus account executive or distributor. Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
System Documentation System Documentation When you receive your system, you will receive a printed copy of the Stratus ftServer 3300: Installation Guide (R528), Stratus ftServer 5600: Installation Guide (R539), or Stratus ftServer 6600: Installation Guide (R542). You can order additional copies of the system documentation set, consisting of these printed documents and the StrataDOC ftServer CD (part number R002FCDK).
Page 22
Use ftServer Management Console (ftSMC) to administer or troubleshoot an ftServer system Stratus ftServer Software Availability Monitor the performance of critical ftServer Manager User’s Guide (R007W) system components and the status of user applications Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 23
Notice page and the page numbers. – For online documentation, include the Help subject and topic title. This information will assist Stratus Publications in making any needed changes to the ftServer documentation. Your assistance is most appreciated.
Page 24
System Documentation 1-10 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
310-D standard. For ftServer 6600 systems, use a cabinet that is either 24U or 38U high. For ftServer 3300 and 5600 systems, use a cabinet that is either 25U or 42U high. Cabinet Requirements for ftServer 3300, 5600, and 6600 Systems Make sure that: •...
The distance between the front and rear vertical rails is between 25 in. and 30 in. (63.50 cm and 76.20 cm). • The vertical mounting rails accept M-5 cage nuts and mounting hardware. Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Rack Requirements Figure 2-1 shows the required rail clearance between the front vertical rails and the inside edge of an accessory leg. Figure 2-1. Rail Clearance 0.5-inch (1.27-cm) 0.5-inch minimum minimum msys182 Front vertical EIA rail Accessory leg Front of cabinet Cabinet and Monitor Requirements...
Monitor Requirements Monitor Requirements If you are using a monitor that is not supplied by Stratus, make sure that: • The monitor accepts universal 100–240 VAC, 50–60 Hz power. • The VGA cable has a 15-pin D-sub connector. • The power cord for the monitor is long enough to reach the power source.
• “Planning for Cables” on page 3-2 Room Requirements If you have ordered an ftServer 6600 system already assembled in a Stratus cabinet, Table A-1, which provides the dimensions of the 24U and 38U cabinets. Otherwise, determine the dimensions of the cabinet in which you will install the system.
Make sure that any cables you plan to connect to the system are long enough to reach between the system and external components or connections. Table 3-1 lists the cables Stratus supplies and, for space planning, specifies the lengths of each cable. Table 3-1. Cables Supplied by Stratus Component Cable Description...
Page 31
Planning for Cables Table 3-1. Cables Supplied by Stratus (Continued) Component Cable Description Length Second tape drive in One SCSI-3 daisy chain cable with a 68-pin 3 ft (91.5 cm) a T522 tape drive SCSI-3 connector at each end enclosure, or second...
Page 32
Planning for Cables Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
• “Power Outlet Requirements” on page 4-5 • “Connecting a System Directly to Two Separate Power Sources” on page 4-7 • “Stratus-Supplied Power Cords” on page 4-9 Related Topics • Chapter 5, “UPS Planning” • Chapter 7, “ftServer Rack Configuration Planning”...
200–240V; 50 Hz Table 4-17. Rack-mountable system that 100–127V; 50 Hz For Japan, NEMA 5-15. does not connect to a PDU 200–240V; 50 Hz For other countries, see Table 4-17. Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
AC Power Service Requirements Table 4-3. ftServer 3300 Systems: AC Power Service Requirements (Continued) Nominal Input Voltage; Frequency Component Range Receptacle Rack-mountable system that 200–240V; 50–60 Hz Table 4-17 does not connect to a PDU High leakage current Table 4-18.
(Extended) ftServer 6600 system 1300 ftServer 5600 system ftServer 3300 system D540 storage enclosure V128 1U LCD unit KVM switch T521 and T522 tape drive enclosure TOTAL A-SIDE POWER REQUIREMENTS Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
@ Power AC Power System Component Quantity (Watts) (Extended) ftServer 6600 system ftServer 5600 system ftServer 3300 system D540 storage enclosure TOTAL B-SIDE POWER REQUIREMENTS Table 4-7. Worksheet for Determining External Power Requirements @ Power AC Power System Component Quantity...
Table 4-10. Worksheet: A-Side External Power Outlet Requirements - No PDUs Component Quantity Outlets Subtotal Systems Monitors Storage enclosures T521 and T522 tape drives TOTAL NUMBER OF A-SIDE POWER OUTLETS Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Connecting a System Directly to Two Separate Power Sources Table 4-11. Worksheet: B-Side External Power Outlet Requirements - No PDUs Component Quantity Outlets Subtotal Systems Monitors Storage enclosures T521 and T522 tape drives TOTAL NUMBER OF B-SIDE POWER OUTLETS Connecting a System Directly to Two Separate Power Sources If you do not connect the ftServer system or PDUs to a UPS, provide two AC power sources that are as electrically independent of each other as the installation site allows.
AC power outlets Figure 4-3 shows the power connections for a pedestal ftServer 3300 system connected directly to two separate power sources. Figure 4-3. Pedestal ftServer 3300 Systems Connected Directly to AC Power s4u090 System power receptacles AC power outlet...
5600 systems • ftServer 3300 systems • PDUs for ftServer 6600 systems • PDUs for ftServer 3300 and 5600 systems • Monitors, KVM switches, tape drives, and storage enclosures • External modems W A R N I N G Place all power cords out of the way of foot traffic.
Table 4-14. ftServer 5600 System Power Cords: 200 240V and 50 60 Hz Current Locale Plug Type Rating Length Marketing ID International NEMA L6-20 4.5m B50161-45M International IEC 309 4.5m B50153-45M 4-10 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
3300 systems directly to an AC power source (not to a PDU or to a UPS). Table 4-19 lists the power cords that connect ftServer 3300 systems to APC Smart-UPS and APC Symmetra UPS models. –...
Marketing ID International NEMA L6-20 4.5m B50161-45M International IEC 309 4.5m B50153-45M Table 4-19. ftServer 3300 Systems: Power Cords to Connect Systems to a UPS Locale Voltage Rating Plug Types Marketing ID North America (Chicago) 120V IEC 320 C13 to B50104-15...
Stratus-Supplied Power Cords ftServer 6600 Systems: PDU Power Cords The AA-P41105 PDU supplies power to ftServer 6600 systems. Table 4-20 describes the permanently attached power cords that supply power to the AA-P41105 PDU. These cords are 12 ft (3.7m) long.
AA-P41104 PDUs to the APC Smart-UPS and APC Symmetra UPS models. These power cords are supplied for ftServer 5600 systems. Table 4-22. ftServer 3300 and 5600 Systems: Power Cords to Connect PDUs to AC Power Current Locale...
Stratus-Supplied Power Cords Power Cords for Monitors, KVM Switches, and Tape Drives Table 4-25 lists the specifications of the power cords that connect monitors, KVM switches, and tape drives directly to external AC power sources. Table 4-25. Monitor, KVM Switch, and Tape Drive Power Cords...
6.5 ft (2.0m) AK-000377 CEE 7 VII Iceland, Sweden 250V/10A, plug type 6.5 ft (2.0m) AK-000378 CEE 7 VII India 250V/10A, plug type 6.5 ft (2.0m) AK-000379 CEE 7 VII 4-16 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 49
Stratus-Supplied Power Cords Table 4-26. External Modem Power Cords (Continued) Marketing Locale Description Length United Kingdom, Ireland 250V/10A, plug type 6.5 ft (2.0m) AK-000380 BS1363/A Italy 250V/10A, plug type 6.5 ft (2.0m) AK-000381 CEI 23-16 Netherlands 250V/10A, plug type 6.5 ft (2.0m)
Page 50
Stratus-Supplied Power Cords 4-18 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Qualified APC UPS Models Stratus has qualified certain UPS models from American Power Conversion Corporation (APC) for use with ftServer systems. For a list the qualified UPS models for ftServer 3300, 5600, and 6600 systems, see one of the following: –...
† To convert an output connector panel to two IEC 309 30R connectors for 30A electrical connectivity to the PDU, obtain an SYPD9 output conversion kit from APC and an AW-B50172-01M interface cable from Stratus. Contact your distributor for availability of the interface cable. Table 5-4. APC Symmetra Tower Models for ftServer 6600 Systems Output Rating;...
Rest of the world Model SUA2200RMI2U 230V APC UPS Models for Use with Multiple ftServer 3300 and 5600 Systems Table 5-6 lists the APC Symmetra models to use when you connect PDUs or multiple ftServer 3300 or 5600 systems to the UPS.
Smart-UPS models to use with a single rack-mountable ftServer 3300 system. Table 5-8 lists the Smart-UPS models to use with a single pedestal ftServer 3300 system. Table 5-7. APC UPS Models for a Single Rack-Mountable ftServer 3300 System...
UPS to the A-side PDU that supplies power to ftServer 6600 systems. N O T E A UPS is required if you use PDUs to supply power to ftServer 6600 systems. Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Connecting the A-Side PDU to a UPS Figure 5-1. ftServer 6600 System: A-Side PDU Connected to a UPS s10u052 A-side PDU A-side PDU power cord B-side PDU B-side PDU power cord UPS power cable A-side system power cables AC power outlet B-side system power cables AC power (mains) distribution circuit breaker...
Figure 5-2 shows how to connect a UPS to the A-side PDU that supplies power to rack-mountable ftServer 3300 and 5600 systems. Figure 5-2. ftServer 3300 and 5600 Systems: A-Side PDU Connected to a UPS s6u104 A-side PDU A-side PDU power cord...
Connecting ftServer Systems Directly to a UPS Connecting ftServer Systems Directly to a UPS The A-side power connector of ftServer systems can be connected directly to a UPS. Figure 5-3 shows how to connect a UPS directly to an ftServer 6600 system. Figure 5-3.
Figure 5-4 shows how to connect a UPS directly to a rack-mountable ftServer 3300 or 5600 system. (An ftServer 3300 system is shown, but the connections are identical for both systems.) Figure 5-4. ftServer 3300 or 5600 Systems: A-Side Power Directly Connected to a UPS...
Connecting ftServer Systems Directly to a UPS Figure 5-5 shows how to connect a UPS to a pedestal ftServer 3300 system. Figure 5-5. Pedestal ftServer 3300 Systems: A-Side Power Directly Connected to a UPS s4u100 System power receptacles A-side system power cord...
Page 62
Connecting ftServer Systems Directly to a UPS 5-12 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
2. If you have a unique network requirement, contact Stratus Professional Services.For a list of available services, see http://www.stratus.com/services/ps/offerings.htm. 3. See the Stratus ftServer: PCI Adapter Guide (R461) for more information about the adapters Stratus supplies for ftServer systems. Network and Telephone Line Planning...
In addition to Ethernet cables, plan to accommodate cables from any U486 Eight-Port Asynchronous PCI Adapters in the system. The U486 PCI adapters are paired and each adapter uses an eight-port fan-out cable with DB-25 connectors, which Stratus supplies. Telephone Line Requirements Generally, an ftServer system requires two telephone lines: •...
Make sure that only layer 1 and layer 2 devices separate the gateway and slave systems. During a connection, the gateway system assigns the slave system a temporary IP address from an IP address range reserved by Stratus and uses that address for all traffic.
Page 66
Site Planning for Systems in an ftGateway Group Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Systems and storage enclosures have two power receptacles. Correspondingly, two power distribution units (PDUs) provide power to the receptacles. Use of PDUs is optional unless you have a support agreement with Stratus. If so, use pairs of power distribution units (PDUs) to provide AC power to systems and components in a cabinet if six or more power cords would otherwise exit from the cabinet.
A-side PDU, complete the information in Table 7-2 to determine the current ftServer 3300 or 5600 systems and components will draw and whether you need a second pair of PDUs. To determine the A-side power usage...
Using PDUs 3. In Table 7-2, for the first component in the table, write the same value in column 3 that you entered in column 2. For subsequent components, add the wattage of the new component to the subtotal in the previous row and write it in column 3. 4.
A-side PDU. The A-side PDU can support four ftServer 3300 systems, three D540 storage enclosures, the V128 1U LCD unit, and the KVM switch. Adding the fourth D540 storage enclosure trips the 15A limit and would require a second pair of PDUs.
Using PDUs Determining A-Side PDU Power Outlets Usage Make sure that ftServer 3300 or 5600 systems and components consume no more than the eight power outlets supported by the A-side PDU. To determine the number of A-side PDU power outlets used 1.
Determining Rack Space Usage Determining Rack Space Usage Make sure that the ftServer 3300 or 5600 systems and components fit into the vertical space available in the rack. To determine the vertical space used 1. In the Quantity column of Table 7-5, enter the number of each component.
Supported ftServer 6600 Cabinet Configurations Supported ftServer 6600 Cabinet Configurations The following figures show combinations of ftServer 6600 systems and optional components that are supported. N O T E S 1. The illustrations show where to place filler panels between components, but be sure to fill the rack above the components with filler panels and, if you do not use PDUs, fill the bottom 2U with filler panels.
“ftServer 6600 System Specifications” on page A-2 • “ftServer 5600 System Specifications” on page A-6 • “Pedestal ftServer 3300 System Specifications” on page A-10 • “Rack-Mountable ftServer 3300 System Specifications” on page A-13 N O T E The system temperature and humidity requirements,...
24U and 38U shipping container and of the unpacked 24U and 38U cabinets. Table A-2 lists specifications for the ftServer 6600 system. Figure A-1. ftServer 6600 System - Front View s10u004 Core I/O enclosures CPU enclosures Expansion I/O enclosures Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
ftServer 6600 System Specifications Figure A-2. ftServer 6600 System - Rear View s10u150 SCSI port ftServer Access Adapter Ethernet port ftServer Access Adapter modem port 10/100/1000-Mbps Ethernet port 10/100-Mbps Ethernet port Serial ports USB ports VGA (monitor) port Power receptacles System Specifications...
Power Output wattage A-side power: 1300 W (AC) B-side power: 900 W (AC) Nominal input voltage; Frequency 200–240 volts AC; 50-60 Hz Physical Dimensions Height 17.75 in. (45 cm; 10U) Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 89
ftServer 6600 System Specifications Table A-2. ftServer 6600 System Specifications (Continued) Width 19 in. (48.26 cm) Depth (including ejectors) 30.9 in. (78.5 cm) Weight 310 lb (141 kg) Environmental Requirements ° ° ° ° Operating temperature F to 95 F (5 C to 35 For every 800 ft (243.8m) above 2,000 ft (609.6m), °...
ftServer 5600 System Specifications Figure A-4. ftServer 5600 System - Rear View s6u089 SCSI port ftServer Access Adapter (optional) Ethernet port ftServer Access Adapter (optional) modem port 10/100/1000-Mbps Ethernet port 10/100-Mbps Ethernet port Serial ports USB ports VGA (monitor) port Power receptacles System Specifications...
4500 BTUs per hour Features Processors One or two Intel Xeon processors in each CPU enclosure Memory Six dual data rate (DDR) inline memory module (DIMM) slots in each CPU enclosure Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 93
ftServer 5600 System Specifications Table A-3. ftServer 5600 System Specifications (Continued) Ports One 10/100-Mbps Ethernet port, one 10/100/1000-Mbps Ethernet port, and one external SCSI port on each core I/O enclosure Two AC power connectors, one VGA port, two serial ports, and two USB ports PCI slots One 32-bit 66MHz PCI slot for a video adapter or ftServer...
Pedestal ftServer 3300 System Specifications Pedestal ftServer 3300 System Specifications Figure A-5 shows the front of a pedestal ftServer 3300 system, its bezel pulled forward. Figure A-6 shows the rear of a pedestal ftServer 3300 system, specifying the locations of the connectors at the back of the system.
Pedestal ftServer 3300 System Specifications Figure A-6. Pedestal ftServer 3300 System - Rear View s4u102a SCSI port ftServer Access Adapter (optional) Ethernet port ftServer Access Adapter (optional) modem port 10/100/1000-Mbps Ethernet port 10/100-Mbps Ethernet port Power receptacles Serial ports USB ports...
One 10/100-Mbps Ethernet port, one 10/100/1000-Mbps Ethernet port, and one external SCSI port on each core I/O enclosure Two AC power connectors, one VGA port, two serial ports, and two USB ports A-12 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Figure A-8 shows the rear of a rack-mountable ftServer 3300 system, specifying the locations of the connectors at the back of the system. Table A-5 lists the specifications for the rack-mountable ftServer 3300 system.
V128 LCD monitor, which contains an integrated keyboard and trackpad. Table B-2 lists the specifications for the V128 LCD monitor. Figure B-2. V128 LCD Monitor Rear Front v128001 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
V115 Keyboard Specifications Table B-3. V129 LCD Monitor Specifications (Continued) Environmental ° ° ° ° Operating temperature F to 95 F (5 C to 35 ° ° ° Storage temperature F to +113°F (5 C to 45 Relative humidity during operation 30% to 80% (noncondensing) Relative humidity during storage 5% to 90% (noncondensing)
AAP41105 power distribution unit (PDU) you can use to supply power to ftServer 6600 systems and optional rack-mountable components. Table B-5 lists the specifications for the AAP41105 PDU. Figure B-4. AAP41105 PDU pdu41150a Power cord (input) Power cord (output) Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
AAP41104 PDU Specifications AAP41104 PDU Specifications Figure B-5 illustrates the AAP41104 PDU you can use to supply power to ftServer 3300 and 5600 systems and optional rack-mountable components. Table B-6 lists the specifications for the AAP41104 PDU. Figure B-5. AAP41104 PDU...
Physical Dimensions Width (front) 19 in. (48.26 cm) Width (rear) 16.75 in. (42.55 cm) Depth 10 in. (25.4 cm) Height 1.75 in. (4.45 cm; 1U) Weight 5 lb (2.27 kg) B-12 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 113
AK470 KVM Switch Specifications Table B-7. AK470 KVM Switch Specifications (Continued) Environmental ° ° ° ° Operating temperature F to 100.4 F (0 C to 38 0 to 2000 ft (0 to 609.6m) ° ° ° ° Storage temperature F to 140 F (-30 C to 60 Relative humidity during operation...
° ° ° Storage temperature F to 140 F (-20 C to +60 Relative humidity during operation 20% to 80% (noncondensing) Relative humidity during storage 10% to 90% (noncondensing) B-14 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
T521 and T522 Tape Drive Enclosure Specifications T521 and T522 Tape Drive Enclosure Specifications Figure B-8 illustrates the T521 and T522 rack-mountable tape drive enclosures. The T521 enclosure contains a single tape drive and the T522 enclosure contains two tape drives.
Power Output wattage Nominal input voltage; Frequency range 100–240 volts AC; 50–60 Hz Physical Height 1.00 in. (2.5 cm) Width 4.25 in. (10.8 cm) Depth 5.60 in. (14.2 cm) B-18 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Appendix C Electrical Circuit and Wiring Information For electrical circuit and wiring information you need to provide to the contractor and/or facilities personnel responsible for wiring the power at the system installation site, see: • “Fault Protection Requirements” on page C-1 •...
Figure C-1. Star Ground Example To monitor To ftServer system Earth reference ground (0V) Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Circuit Wiring Diagrams Circuit Wiring Diagrams The following circuit wiring diagrams show how the hot, ground, and/or neutral AC signals should be connected to the system’s power input plug: • Figure C-3 illustrates a single-phase 120V AC circuit connection (for ftServer 5600 and 3300 only).
Figure C-3. Single-Phase 120V AC Circuit Connection Circuit A or B 120V G (PE) 15A Maximum Wall Power Cord G (PE) To power input A or B Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Circuit Wiring Diagrams Figure C-4 shows a single-phase 240V AC circuit connection. Note that this application requires a single-pole circuit breaker. Figure C-4. Single-Phase 240V AC Circuit Connection Circuit A or B 240V G (PE) Single system: 20A maximum PDU: 30A maximum Wall Power Cord G (PE)
Figure C-5. Split-Phase 120/240 Volts AC Circuit Connection 240V Circuit A or B 120V 120V G (PE) Single system: 20A maximum PDU: 30A maximum Wall Power Cord G (PE) To power input A or B Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 125
Circuit Wiring Diagrams ∆ Figure C-6 shows a three-phase 208V AC, Y-, or -source circuit connection, which is a phase-to-neutral source connection. Note that the ftServer X input can be connected from L1, L2, or L3. This application requires a single-pole circuit breaker. ∆...
Page 126
-Source Circuit Connection, Phase-to-Phase 208V 120V 208V 120V Circuit A or B 120V G (PE) Single system: 20A maximum PDU: 30A maximum Wall Power Cord G (PE) To power input A or B Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
G (PE) To power input A or B Electrical Power Connectors Table C-1 describes the connectors that Stratus uses to connect the ftServer systems and its peripheral devices, such as tape drives, to AC power outlets. Electrical Circuit and Wiring Information...
20A, 208/24 volts AC 2-pole, 3-wire NEMA 5-15 15A, 125 volts AC 2-pole, 3-wire NEMA L6-30 30A, 125/25 volts AC 2-pole, 3-wire CEE (7) VII 20A, 25 volts AC 2-pole, 3-wire C-10 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 129
Electrical Power Connectors Table C-1. Connectors for AC Power Outlets (Continued) Connector Configuration Rating Description ‡ BS 89 3 13A or 10A, 25 volts 2-pole, 3-wire CEI-23-16 16A, 25 volts AC 2-pole, 3-wire SI 32/1971 16A, 25 volts AC 2-pole, 3-wire IEC-309 16-20A, 200-24 volts 2-pole, 3-wire...
Page 130
3112-1993 † ftServer 6600 only ‡ ftServer 6600 only § ftServer 3300 and 5600 ¶ ftServer 3300 and 5600 †† ftServer 3300 and 5600 ‡‡ ftServer 3300 and 5600 C-12 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Electromagnetic compatibility (EMC) regulations. 3. All EMC emissions compliance tests are performed at a third-party certified test laboratory. You can obtain compliance reports for these tests from your Stratus account representative, who will contact the Product Compliance Group in the Stratus engineering organization.
ISO 9614-2 Acoustics. Determination of Sound Power European Union Levels of Noise Source using Sound Intensity ISO 7779 Measurements of Airborne Noise emitted by European Union Computers and Business Equipment Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
B-14 USB, 3-2 ftGateway group VGA, 3-2 site planning for, 6-3 Y-style modem, 3-3 ftServer 3300 systems power service requirements, 4-2 getting assistance, 1-2 ftServer 5600 systems checklist for site planning, 1-2 power service requirements, 4-2 circuit connections, C-3...
Page 136
D540 storage enclosure, B-2 external modem, B-18 PDUs ftServer 3300 AAP41104 specifications, B-10 pedestal system, A-10 AAP41105 specifications, B-8 rack-mountable system, A-13 connecting to ftServer 3300 systems and ftServer 5600 system, A-6 Index-2 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)
Page 137
120/240V AC circuit V128 LCD monitors connection, C-6 power service requirements, 4-3 standards compliance, D-1 specifications, B-4 Stratus Customer Assistance Center. See CAC V129 LCD monitors system power cords, 4-15 power service requirements, 4-3, 4-5 specifications, B-6 VGA cables, 3-2...
Page 138
Index Index-4 Stratus ftServer 3300, 5600, and 6600: Site Planning Guide (R553)