LG PSF1032A Service Manual page 8

Plasma lighting system
Hide thumbs Also See for PSF1032A:
Table of Contents

Advertisement

※ ※ Power condition and switchboard configuration for PLS installation
• Because the power consumption per 1 set of PLS is high, the cross sectional area of the
switchboard must appropriately be applied, and for stable operation, one control switch must be
installed for each set.
• Grounding requires more than 3 grounding points and must be wired for safety purposes.
14.0 mm
or above
* PLS is not equipped with a terminal block. For installation, please get professional assistance.
- Terminal Block Specification
(a) Rated Voltage: 250V or above
(b) Rated Power: 10A or above
(c) 3 way bolt fastening type
- After connecting power line to the terminal block, ensure that the power line makes secure
contact with fastening bolt or clamp and the power line is securely fastened.
WARNING
• After wiring power line to terminal box, check if the line touches tightening bolt or clamp or
is being forced.
• Use regulated electric wire so connecting part of terminal is knocked out by external force.
It can cause fire if connecting part is fixed tightly as it generates heat.
• Wire power line after ring terminal work. It can cause fire and failure of electric parts.
• Check Neutral status when installing main power
• Ending part of PLS has to be waterproof when connecting it to terminal.
Note)
MCCB: Molded Case Circuit Breaker
ELB: Earth Leakage Circuit Breaker
Use rate sensitivity current (Break current) of 30 [mA]
MS: Magnetic Switch (Used when applying GPS or auto flash device)
PLS switchboard
(When installing 6 sets)
MCCB
75A or
above
Apply
2
Recommended to
apply ELB, MS
capacity of 10A
Apply 2.0 mm
2
or above for
each line
8