Set The Esp; Electric Wiring Work - York YDCC06-45 Installation Manual

Vrf
Table of Contents

Advertisement

Fig. 10 Duct Connection
NO
CAUTION
TE
z Wrap both the inlet-side and outlet-side flange and
the duct connection area with aluminium tape for
something similar to prevent air escaping.
z Please attach an air filter inside the air passage on
the inlet-side. (Use an air filter which duct
collection efficiency (in a gravimetric technique) is
higher than 50%)
z Be sure to insulate the duct to prevent condensate
water from forming. (Material: glass wool or
polyethylene foam, above 25mm thickness)
z Duct pressure drop of YDCC06~18/YDCC018~053
indoor unit models cannot be higher than 30 Pa;
YDCC25~45/YDCC066~115 indoor unit models
cannot be higher than 80 Pa;
YDCC50~60/YDCC140~175 indoor unit models
cannot be higher than 100 Pa.
z The air outlet cannot be too high and be positioned
at the place where it directly blows the people for a
long period.
z To reduce vibration and noise, it is better to use
flexible connection to connect the air inlet and
outlet duct with indoor unit.

9 SET THE ESP

z YDCC06~18/YDCC018~053 indoor unit models' ESP
(External Static Pressure) can be divided as 3 types
– 0 Pa, 15 Pa and 30 Pa;
10.2 Electrical parameters
Indoor unit power supply and Max operation current
Indoor Unit Model
BTU type
kW type
YDCC06 09
YDCC018 025
YDCC12 25
YDCC034 066
YDCC30 45
YDCC078 115
YDCC50
YDCC140
YDCC60
YDCC175
YORK VRF Air-Conditioner IOM
z Indoor unit ESP can be adjusted by changing the

10 ELECTRIC WIRING WORK

10.1 General introduction
z Shut off the power before doing any work.
z All field supplied parts and materials and electric
z All wiring works should be performed by specially
z Install a wiring interrupter or ground-fault circuit
z Be
z Be sure the air-conditioner is well grounded. Never
z Do not turn on the power sully unless all the work
z Wiring of different thickness or diameter cannot be
z For wiring, please use the designated power supply
z The terminal screw should not be tightened too
Power Supply
H0 type
(or Cooling Only)
0.26
0.85
220V
50Hz
1.31
2.8
3.18
7
YDCC25-45/YDCC066-115 indoor unit models' ESP
(External Static Pressure) can be divided as 3 types
– 15 Pa, 40 Pa and 100 Pa;
YDCC50~60/YDCC140~175 indoor unit models' ESP
(External Static Pressure) can be divided as 3 types
– 15 Pa, 50 Pa and 100 Pa;
Out factory state, YDCC indoor unit ESP is 15 Pa
(default value). User can adjust the ESP according
to the actual pressure drop of the air duct.
connection site of fan wiring in the control board.
For detail setting method of different indoor ESP,
please refer to the wiring diagram attached to the
control box lid.
works must conform to local laws.
qualified electricians.
interrupter for the power supply wiring.
connect the ground line with gas pipe, water pipe,
lightning conductor or telephone lines.
has been done.
connected to one power supply wiring terminal.
wiring and connect firmly, then secure to prevent
external pressure being exerted on the terminal
board.
hard or too loose. Too hard may damage the
terminal board and too loose may result in bad
connection and danger due to terminal board
overheating.
Max Operation Current(A)
H2 type
4.76
8.15
10.31
-
-
H4 type
-
9.85
15.81
-
-