Honeywell TB3026B Installation Instructions Manual page 6

Bacnet fixed function thermostat for fan coil/heat pump/conventional systems
Table of Contents

Advertisement

BACNET® FIXED FUNCTION THERMOSTAT
ISU Parameter
Code
120
Year, first 2 digits
130
Year, second 2 digits
140
Month
150
Day
160
Schedule format BV-133 0 – not programmable (BV-133=0) 4 – 7 day programmable (BV-133=1)
280
Backlight control BV-79 0 – on for 20 seconds after keypress
320
Swap English/Metric
BV-69
330
Daylight saving
AV-127
500
Filter change reminder
AV-124
510
Hum pad change
reminder
AV-125
520
UV lamp change
reminder
AV-126
540
Program periods
AV-129
640
Clock format
BV-83
670
Keypad lock
AV-128
700
Sensed room
temperature offset (AV-
138)
701
Sensed room humidity
offset (AV-139)
702
Sensed outside air
temperature offset (AV-
140)
703
Sensed outside humidity
offset (AV-141)
800
MS/TP MAC
801
BACnet Device Instance
- first digit
802
BACnet Device Instance
second and third digits
803
BACnet Device Instance
forth and fifth digits
804
BACnet Device Instance
sixth and seventh digits
31-00093—01
Table 3. ISU Parameters.
Description
19-21
00-99 (00-54 if ISU 200=21)
1-12
1-31
1 – low always on, bright after keypress
1 – show opposite units to specified in DDC header
0 – off; no automatic adjustments
1 – pre 2007 scheme
2 – 2007 and later scheme
0 – reminder not used
1 – 10 days
2 – 30 days
3 – 60 days
4 – 90 days
5 – 120 days
6 – 365 days
0 – reminder not used
1 – 90 days
2 – 180 days
3 – 365 days
0 – reminder not used
1 – 365 days
2 – Wake/Sleep
4 – Wake/Leave/Return/Sleep
12 – 12 hour (BV-83=0)
24 – 24 hour (BV-83=1)
0 – no lock
1 – access temperature settings only
2 – fully locked
-4 to +4 degrees F
-5% TO +5%
Humidity cannot be adjusted above 100% or below 0%.
-4 to +4 degrees F
-5% TO +5%
Humidity cannot be adjusted above 100% or below 0%.
0-127
0-4
00-99
00-99
00-99
Allowed Values
6