Electrical installation

What this chapter contains

The chapter describes the electrical installation procedure of the drive.
WARNING! The work described in this chapter may only be carried out by a qualified
electrician. Follow the instructions in chapter
instructions can cause injury or death.
Make sure that the drive is disconnected from the input power during
installation. If the drive is already connected to the input power, wait for 5
minutes after disconnecting the input power.

Checking the insulation of the assembly

Drive
Do not make any voltage tolerance or insulation resistance tests (e.g. hi-pot or
megger) on any part of the drive as testing can damage the drive. Every drive has
been tested for insulation between the main circuit and the chassis at the factory.
Also, there are voltage-limiting circuits inside the drive which cut down the testing
voltage automatically.
Input cable
Check the insulation of the input cable according to local regulations before
connecting to the drive.
Motor and motor cable
Check the insulation of the motor and motor cable as follows:
1. Check that the motor cable is connected to the motor and disconnected from the
drive output terminals U2, V2 and W2.
M
ohm
2. Measure the insulation resistances of the motor cable and the motor between
each phase and the Protective Earth by using a measuring voltage of 1 kV DC.
PE
The insulation resistance must be higher than 1 Mohm.
Safety
on page 5. Ignoring the safety
29
Electrical installation