Mitsubishi Electric PUHZ-P200YKA.UK Service Manual page 72

Table of Contents

Advertisement

SW2 setting
Capacity save
0 to 100
When air conditioner is connected to
M-NET and capacity save mode is
ON
demanded, a value from "0" to "100" is
displayed.
1
2 3 4 5 6
When there is no setting of
capacity save, "100" is displayed.
Error postponement code history (2)
of outdoor unit
ON
1
2 3 4 5 6
Error postponement code history (3)
of outdoor unit
ON
1
2 3 4 5 6
Error history (3) (Oldest)
ON
Alternate display of abnormal unit num-
ber and code.
1
2 3 4 5 6
Error thermistor display
ON
When there is no error thermistor,
"–" is displayed.
1
2 3 4 5 6
Operation frequency on error occurring
0 to 255
ON
1
2 3 4 5 6
Fan step on error occurring
0 to 10
ON
1
2 3 4 5 6
Indoor room temperature (TH1) on error
occurring
ON
8 to 39
1
2 3 4 5 6
OCH582B
Display detail
The black square ( ) indicates a switch position.
Explanation for display
0 to 100
(When the capacity is 100% hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 100%;
0.5 s 0.5 s 2 s
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
Postponement code display
Blinking: During postponement
Lighting: Cancellation of postponement
"00" is displayed in case of no postponement.
When no error history, "0" and "– –" are displayed by
turns.
3: Outdoor pipe temperature/Liquid (TH3)
6: Outdoor pipe temperature/2-phase (TH6)
7: Outdoor Ambient temperature (TH7)
8: Outdoor Heat sink (TH8)
0 to 255
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 125Hz;
0.5 s 0.5 s 2 s
0 to 10
8 to 39
72
1
00
1
25
Unit
%
Code
display
Code
display
Code
display
Code
display
Hz
Step
: