Outdoor Unit Operation Monitor Function - Mitsubishi Electric PUHZ-P200YKA.UK Service Manual

Table of Contents

Advertisement

<Outdoor unit operation monitor function>
[When optional part 'A-Control Service Tool (PAC-SK52ST)' is connected to outdoor controller board (CNM)]
Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of check code by
controlling DIP SW2 on 'A-Control Service Tool'.
Operation indicator SW2 : Indicator change of self diagnosis
SW2 setting
ON
1
2 3 4 5 6
<Digital indicator LED1 working details>
(Be sure that the 1 to 6 in the SW2 are set to OFF.)
(1) Display when the power supply ON
When the power supply ON, blinking displays by turns.
Wait for 4 minutes at the longest.
(2) When the display lights (Normal operation)
1 Operation mode display.
LED1
The tens digit: Operation mode
Display
Operation Model
O
OFF/FAN
C
COOLING/DRY *
H
HEATING
d
DEFROSTING
*C5 is displayed during replacement operation.
2 Display during error postponement
Postponement code is displayed when
compressor stops due to the work of
protection device.
Postponement code is displayed while
error is being postponed.
(3) When the display blinks
Inspection code is displayed when compressor stops due to the work of protection devices.
Display
Inspection unit
0
Outdoor unit
1
Indoor unit 1
2
Indoor unit 2
3
Indoor unit 3
4
Indoor unit 4
Display Contents to be inspected (When power is turned on)
63H connector(yellow) is open.
F5
E8
Indoor/outdoor communication error (Signal receiving error) (Outdoor unit)
Indoor/outdoor communication error (Transmitting error) (Outdoor unit)
E9
Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more)
EA
Miswiring of indoor/outdoor unit connecting wire(converse wiring or disconnection)
Eb
Startup time over
EC
Communication error except for outdoor unit
E0–E7
OCH582B
Display detail
(Lighting)
The ones digit: Relay output
Display
0
1
2
3
4
5
6
7
8
A
Display
Contents to be inspected (During operation)
U1
Abnormal high pressure (63H operated)
U2
Abnormal comp. surface thermistor, shortage of refrigerant
Open/short circuit of comp. surface thermistor(TH32)
U3
Open/short of outdoor unit thermistors (TH3, TH6, TH7 and TH8)
U4
Abnormal temperature of heat sink
U5
Abnormality of power module
U6
Abnormality in outdoor fan motor
U8
Overheat protection
Ud
UF
Compressor overcurrent interruption (When Comp. locked)
UH
Current sensor error
UL
Abnormal low pressure
UP
Compressor overcurrent interruption
PL
Abnormality of refrigerant
Abnormality of indoor units
P1–P8
Communication error of M-NET system
A0–A7
67
Explanation for display
1 second
interval
ON
1
Warming-up
Compressor
Compressor
ON
ON
ON
ON
ON
ON
SW2
(Initial setting)
2 3 4 5 6
4-way valve
Solenoid valve
ON
ON
ON
ON
ON
ON
ON
ON
ON
Unit

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Puhz-p250ykar1.ukPuhz-p250yka.ukPuhz-p200ykar1.uk

Table of Contents