Output Connections; Table 2.1 - Mantracourt ICA3 User Manual

Strain gauge or load cell embedded analogue amplifier
Hide thumbs Also See for ICA3:
Table of Contents

Advertisement

Table 2.1

This typical cable data is provided for information only.
The cable should have 2 x twin twisted cables. Ideally each pair should be individually shielded and with an overall
shield.
Country
Supplier
UK
Farnell
UK
Farnell
UK
RS
If possible segregate the signal cable from Power Cables; allow a 1metre (3 feet) distance from such cables.
Do not run signal cables in parallel with power cables and cross such cables at right angles.
The ground connection conductor should have sufficient cross-sectional area to ensure a low impedance path to
attenuate RF interference.

Output Connections

The ICA3 and ICA6 S and H versions provide a ±10V output. Other bi-polar outputs can be configured by altering
Resistor R.
Connect the output as shown in Figures 2.2, 2.3 or alternatively Figure 2.4
Mantracourt Electronics Limited ICA3 & 6 S and H Versions User Manual
Part No
Description
118-2117
Individually shielded twisted multipair cable (7/0.25mm)- 2 pair
Tinned copper drain. Individually shielded in polyester tape.
Diameter: 4.1mm
Capacitance/m: core to core 115 pF & core to shield 203 pF
585-646
Individually shielded twisted multipair cable (7/0.25mm)- 3 pair
Tinned copper drain. Individually shielded in polyester tape.
Diameter: 8.1mm
Capacitance/m: core to core 98 pF & core to shield 180 pF
626-4761
Braided shielded twisted multipair cable (7/0.2mm)- 1 pair
Miniature- twin -round Diameter: 5.2 mm
Capacitance/m: core to core 230 pF & core to shield 215 pF
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ica6sIca6h

Table of Contents